Technical guideFree to readYear not stated

ELITUPS single-phase automatic transfer system ATS series, Rev.0

ELIT

A three-page Rev. 0 sheet from Italian manufacturer ELIT Srl describing two models of its 19-inch rack-mount single-phase ATS series: ATS 230 16 (16 A) and ATS 230 32 (32 A). Transfer time between two independent sources is 8-12 ms and efficiency is 99%.

On this page

Overview

The sheet covers the rack-mount automatic transfer switch used to give single-corded IT equipment a redundant supply from two sources. The ATS continuously monitors two independent sources, synchronous or asynchronous; one is assigned as primary and the other as alternate. When the line feeding the load leaves the user-defined voltage or frequency tolerance band, the load is transferred automatically to the other source, and it returns automatically to the preferred source when the line comes back within tolerance. Transfer can also be made manually from the front panel.

The technical table compares the two models. Both take 230 VAC nominal (150-300 VAC) single phase plus neutral at 50/60 Hz, with a frequency tolerance selectable at ±5%, 10%, 15% or 20%. Output is settable at 220/230/240 V ±1%. ATS 230 16 has two IEC 320 C20 inlets and 8 C13 plus 1 C19 outlets, measures 440 x 275 x 44 mm and weighs 3.5 kg. ATS 230 32 uses terminals on the input and 16 C13 plus 2 C19 outlets, measures 440 x 275 x 88 mm and weighs 4 kg.

The sources can be a UPS and another type of source, or two non-UPS sources with sinusoidal output; the sheet states that the highest protection for connected equipment is obtained when both sources are online UPSs. An output circuit breaker is standard and an input breaker is optional. RS232, USB and 5 dry contacts are standard for communication, and the accessory slot takes an SNMP or RS485 card. The optional ITS maintenance base allows the ATS module to be hot-swapped while the load stays fed. A 120 VAC version is also available.

The device is not a static (solid-state) transfer switch: the 8-12 ms transfer time can exceed one half cycle (10 ms at 50 Hz). The hold-up time of IT power supplies typically covers this range, but sensitive loads need checking. Operating temperature is -5 °C to +40 °C and relative humidity 20-90% non-condensing. EN 60950-1 is cited for safety and EN 62310-2, the static transfer systems standard, for EMC, and the product carries the CE mark.

Key points

  1. Models: ATS 230 16 (16 A) and ATS 230 32 (32 A), single phase plus neutral.
  2. Input: 230 VAC nominal, 150-300 VAC range, 50/60 Hz; frequency tolerance selectable at ±5%/10%/15%/20%.
  3. Output: 220/230/240 V ±1%, settable; transfer time 8-12 ms; efficiency 99%.
  4. ATS 230 16: inlet 2 x IEC 320 C20, outlets 8 x C13 and 1 x C19, 440 x 275 x 44 mm, 3.5 kg.
  5. ATS 230 32: terminal input, outlets 16 x C13 and 2 x C19, 440 x 275 x 88 mm, 4 kg.
  6. Protection: output circuit breaker standard, input breaker optional.
  7. Communication: RS232, USB, 5 dry contacts; SNMP or RS485 in the option slot.
  8. Environment: -5 °C to +40 °C, 20-90% relative humidity non-condensing.
  9. Standards: EN 60950-1 (safety), EN 62310-2 (EMC), CE.

Using it in design

  • Use an ATS per rack to connect single-corded equipment (network switch, legacy server, KVM) to the A and B feeds of a 2N distribution, and feed the two inputs from different UPSs.
  • Compare the 8-12 ms transfer time with the hold-up time of the load power supply; for loads with less than 10 ms of hold-up, choose a static transfer switch (STS).
  • Limit rack load to the ATS current rating: at 230 V, 16 A is about 3.7 kVA and 32 A about 7.4 kVA.
  • The ATS is a single point of failure, so specify the ITS hot-swap base for critical racks.
  • In the rack layout, allow 44 mm (1U) for the 16 A model and 88 mm (2U) for the 32 A model with 275 mm depth, and match the outlet count (8+1 or 16+2) to the equipment plug types.
  • Connect source status and transfer events to DCIM through the SNMP card.

Who should read it

Electrical engineers designing rack-level power distribution and IT infrastructure teams connecting single-corded equipment to 2N infrastructure.

Document contents

  1. Features
  2. Principles of Working
  3. Control Panel
  4. Input and Output
  5. Interfaces
  6. Technical table: Input, Output, Protection, Interface, Miscellaneous, Standards

Publication details

Authors
ELIT
Publisher
ELIT
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ELIT ELITUPS single-phase automatic transfer system ATS series, Rev.0. ELIT. https://www.elit-ups.com/wp-content/uploads/2018/04/ELITUPS-Sistemi-di-trasferimento-ATS-inglese.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.