Technical guideFree to readYear not stated

Shinhoo AWZ65-40-200 Horizontal Single Stage Pump

Original title Shinhoo: AWZ65-40-200 technical data

Shinhoo

Shinhoo AWZ65-40-200 is a DN65, 380 V / 50 Hz, 5.5 kW horizontal single-stage wet-rotor pump; the page lists a maximum flow of 48 m³/h and a maximum head of 46 m.

On this page

Overview

The page presents Shinhoo's AWZ65-40-200 horizontal single-stage pump. It works on a wet-rotor system, with hydraulics designed using a 3D impeller and hydraulic simulation and a custom high-efficiency motor. Communication is PWM, protection class IP55 and the connection is chuck type.

The technical table lists DN 65 mm, rated flow 48 m³/h, rated head 46 m, maximum head 40 m, 380 V, 50 Hz, 5,500 W and a port-to-port length of 501 mm. The header gives maximum flow 48 m³/h and maximum head 46 m. Head values are labelled differently between header and table, so selection should rest on the performance curve.

Operating conditions are medium temperature -25 to +110 °C, operating ambient -25 to +55 °C and storage -35 to +60 °C (with no freezing in pipe or pump). Application fields include charging and storage liquid cooling, domestic water supply, hot water circulation and HVAC, and industrial circulation.

Compared with its sibling AWZ65-40-160, the model offers higher flow and head at higher power (5.5 kW against 4 kW). No numerical performance curve appears as text; before use in a data-centre cooling water loop, the curve, NPSH and fluid compatibility should be confirmed with manufacturer data.

Key points

  1. DN 65, 380 V, 50 Hz, 5,500 W, IP55, port-to-port length 501 mm.
  2. Header: maximum flow 48 m³/h and head 46 m; table: rated flow 48 m³/h, rated head 46 m, maximum head 40 m.
  3. Medium temperature -25 to +110 °C; operating ambient -25 to +55 °C; storage -35 to +60 °C.
  4. Wet-rotor system, 3D impeller design and hydraulic simulation.
  5. PWM communication interface; chuck-type connection.
  6. Against AWZ65-40-160, flow rises from 40 to 48 m³/h and power from 4 to 5.5 kW.

Using it in design

  • Compare the performance curve with the duty point rather than relying on the header and table head labels.
  • For glycol loops, ask the manufacturer about viscosity effects across the -25 to +110 °C medium range.
  • Add the 380 V, 5.5 kW supply and IP55 requirement to the electrical design and check starting current separately.
  • For a two-pump duty/standby arrangement, size the common header and the DN65 connections.

Who should read it

Mechanical designers selecting pumps for cooling water loops.

Document contents

  1. Technical data
  2. Application fields
  3. Features and benefits
  4. Performance curves

Publication details

Authors
Shinhoo
Publisher
Shinhoo
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Shinhoo Shinhoo: AWZ65-40-200 technical data. Shinhoo. https://www.shinhoopump.com/awz65-40-200-horizontal-single-stage-pump_p597.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.