Feiyu Cooling Towers and Air Cooled Heat Exchangers Catalogue

Original title Feiyu Cooling Towers and Air Cooled Heat Exchangers

Feiyu

Hebei Feiyu catalogue of closed-circuit, open-circuit and hybrid wet-dry cooling towers plus dry and adiabatic air coolers, with an FYBN model table from FYBN-6 (30,135 kcal/h) to FYBN-600 (3,000,000 kcal/h).

On this page

Overview

The catalogue covers Hebei Feiyu Cooling Equipment Co., Ltd. product groups: counter-flow, cross-flow and mixed-flow closed-circuit towers, open-circuit towers, hybrid wet-dry towers, flat and V-shaped dry air coolers and V-shaped adiabatic coolers. The company reports two factories with 15,000 m2 total building area, two production lines and more than 100 skilled workers. The body is stainless steel 304 or aluminium-zinc coated DX51D+AZ120 sheet; the coil is stainless steel or copper tube; the framework is hot-dip galvanised.

A closed-circuit tower cools process fluid circulating in a coil using spray water and air, so no dirt or foreign matter enters the fluid; it replaces open-circuit towers where cleanliness is required. In counter flow, air moves bottom to top against the spray water; in cross flow, air enters perpendicular to the spray. Low-height forced-fan towers suit indoor and ducted installation. The catalogue states heat rejection of 170-4119 MBH for forced-fan towers and 91-37765 MBH for induced-draft axial-fan towers. Open-circuit towers cost less initially but use more water; hybrid towers cut water use by combining dry and wet operation.

The FYBN performance table holds model, nominal heat rejection (kcal/h), fan count, air flow, fan power, spray pump flow and power, and net and operating weight. FYBN-6: 30,135 kcal/h, 10,000 m3/h, 0.55 kW fan, 287 kg net, 730 kg operating; FYBN-100: 500,000 kcal/h, 52,000 m3/h, 2 x 2.2 kW fans, 1870 kg net, 4100 kg operating; FYBN-600: 3,000,000 kcal/h, 570,000 m3/h, 3 x 11 kW fans, 17,500 kg net, 37,250 kg operating. Spray flow is not process flow. The dry-cooler sections give no model performance table.

Key points

  1. FYBN range: FYBN-6 (30,135 kcal/h) to FYBN-600 (3,000,000 kcal/h).
  2. FYBN-100: 500,000 kcal/h, 52,000 m3/h air, 2 x 2.2 kW fans, 44.5 m3/h spray flow.
  3. FYBN-600: 570,000 m3/h air, 3 x 11 kW fans, 352 m3/h spray flow, 37,250 kg operating weight.
  4. Forced-fan closed towers 170-4119 MBH; induced-draft axial-fan towers 91-37765 MBH.
  5. Body stainless steel 304 or DX51D+AZ120; coil stainless steel or copper; hot-dip galvanised frame.
  6. Closed-circuit tower keeps process fluid clean; open-circuit is cheaper but uses more water.
  7. Catalogue describes flat, V and adiabatic V dry coolers without a performance table; an operating temperature limit of 65 °C is stated.

Using it in design

  • Select closed-circuit towers only after the maker confirms the rating condition; ask the specification to state the water and wet-bulb condition behind the kcal/h value.
  • Do not mix spray pump flow with process flow; they are separate circuits and pump power is added to the electrical load.
  • Use operating weight in roof load and erection planning; large models such as FYBN-600 exceed 37 tonnes.
  • For circuits needing clean process fluid, compare closed-circuit or hybrid towers with open-circuit on water use and first cost.
  • Request separate performance data for dry and adiabatic coolers; the catalogue sections have no model schedule.

Who should read it

Mechanical designers and purchasing engineers selecting closed-circuit towers or dry coolers for data-centre heat rejection.

Document contents

  1. About Feiyu Cooling
  2. Closed circuit cooling towers (counter, cross, mixed flow)
  3. Open circuit cooling towers
  4. Hybrid wet dry cooling towers
  5. Air cooled heat exchangers (flat dry, V dry, V adiabatic)
  6. Our projects

Publication details

Authors
Feiyu
Publisher
Feiyu
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Feiyu Feiyu Cooling Towers and Air Cooled Heat Exchangers. Feiyu. https://www.flycoolingtower.com/pdf/cooling-towers-air-cooled-heat-exchanger.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.