Ablerex Ermes ATS technical data sheet
Ablerex
An Ablerex power quality brochure, Rev. 2024/06, presenting the Ermes rack-mount automatic transfer switches that give single-corded rack equipment a redundant supply from two independent sources: three models (16 A, 32 A and 32 A BP), a transfer time of 8 to 12 ms, and 1U or 2U height.
On this page
Overview
Ermes is a rack-mount automatic transfer system that feeds servers and network devices with a single power input from two separate, independent sources. The brochure names server rooms, data centres, networking equipment and video surveillance and security equipment as applications. Automatic transfer between the two sources takes 8 to 12 ms. Rated voltage is selectable at 200, 208, 220, 230 or 240 V AC; the voltage and frequency tolerance windows can be set to ±5%, 10%, 15% or 20%, and frequency is 50 or 60 Hz.
The three models are given in separate columns. The Ermes 16A is a 1U unit with two IEC C20 inlets and 8 IEC C13 plus 1 IEC C19 outlets. The Ermes 32A offers 12 IEC C13 and 2 IEC C19 outlets plus a 32 A terminal block and takes 2U. The Ermes 32A BP includes a manual bypass and a hot-swappable ATS module, and the brochure states that this version keeps the supply continuous during maintenance. On the 32 A models the input connection is listed as 2 x 30 A terminal blocks, while the maximum output current is 32 A.
RS232, USB, an emergency power off (EPO) input and a relay card with five dry-contact outputs are standard on all models; RS485 and SNMP/web cards are optional. LEDs show the active source and fault status, and the LCD shows parameters and alarms. Operating temperature is -5 to +40 °C. The same brochure also covers Enersine active harmonic filters: wall-mounted models from 30 to 100 A and modular models from 400 to 600 A, harmonic correction from the 2nd to the 51st order and a 25 microsecond response time.
Key points
- Three models: Ermes 16A (16 A), Ermes 32A (32 A) and Ermes 32A BP (32 A, with manual bypass and hot-swappable ATS).
- Transfer time 8 to 12 ms.
- Dimensions (W x D x H): 440 x 275 x 44 mm for the 16A, 440 x 275 x 88 mm for the 32A, 440 x 346 x 88 mm for the 32A BP; weights 4, 6 and 8 kg.
- Outlets: 8 x IEC C13 and 1 x IEC C19 on the 16 A model; 12 x IEC C13 and 2 x IEC C19 on the 32 A models, plus 1 x 32 A terminal block on the 32A.
- Inlets: 2 x IEC C20 on the 16 A model; 2 x 30 A terminal blocks on the 32 A models, with 32 A maximum output current.
- Rated voltage 200/208/220/230/240 V AC, frequency 50/60 Hz; tolerances ±5%, 10%, 15% or 20%.
- Operating temperature -5 to +40 °C, relative humidity 0% to 90% non-condensing; standards IEC EN 62368-1 and IEC EN 62310-2; CE and UKCA marked.
Using it in design
- In racks with single-corded devices, connect the A and B feeds to the Ermes inputs so that those devices also benefit from the redundancy of 2N distribution.
- Compare the 8 to 12 ms transfer time with the power supply hold-up time of the equipment fed.
- Note that the 32 A models list a 30 A input terminal against a 32 A output; settle the feeder protection and cable size with the manufacturer.
- For racks that must not be interrupted during maintenance, choose the 32A BP version with manual bypass and allow for its 346 mm depth in the rack layout.
- Add the SNMP/web card to the specification for remote monitoring and tie the EPO input into the room's emergency power off circuit.
Who should read it
Data-centre engineers designing in-rack power distribution, and operators of network and server rooms.
Document contents
- Ermes ATS
- Key options
- Applications
- ATS technical data sheet
- Enersine APF
- Enersine monolithic technical data sheet
- Enersine modular technical data sheet
Publication details
- Authors
- Ablerex
- Publisher
- Ablerex
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Ablerex Ablerex Ermes ATS technical data sheet. Ablerex. https://ablerex.eu/wp-content/uploads/2024/03/12_BROCHURE_UPS_ERMES-ATS_2025-11_EN_LR.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.