Ablerex STS Technical Data Sheet (Rev.2024/08)

Original title Ablerex STS technical data sheet Rev.2024/08

Ablerex

A manufacturer document giving input, output, overload and environmental data for seven three-phase central static transfer switch models from 100 to 1250 A.

On this page

Overview

The document introduces a family of central STS units that feed single-input equipment from two independent sources. The maximum automatic transfer speed between sources is 5 ms for the 63 A versions and 4 ms for the 100 A and larger versions. If a short circuit occurs downstream, transfer is inhibited automatically so that neither source is damaged. Input voltage and frequency are monitored continuously so that switching happens safely without source cross-over.

Redundancy is built in at component level: source independence and internal redundancy cover the bypass, power supplies and cooling, and a separate dual manual bypass is provided. SCR status is detected in real time and backfeed protection is included. Options include an additional dry-contact card, top cable entry, operation without neutral, a 4-pole configuration with switched neutral and an isolation transformer.

The technical table lists seven three-pole models (100, 250, 400, 630, 800, 1000, 1250 A). Rated voltage is 208/380/400/415/440/480 Vac, voltage tolerance is plus or minus 10% (up to 20% on request), frequency is 50/60 Hz plus or minus 2 Hz, and the switching phase angle is 5 to 30 degrees. Source harmonic voltage content is unlimited; above 20% THD the switching time rises to at most 10 ms, against at most 4 ms normally. Switching is break-before-make and inhibited on fault. Load power factor ranges from 1 to 0.3 and maximum crest factor is 3:1.

Overload capacity is 125% for 30 minutes, 150% for 10 minutes, 200% for 30 seconds, 2000% for one cycle and 4000% for half a cycle, and AC/AC efficiency is above 99%. Units are IP20, operate from 0 to 40 degrees C, need 0.5% derating per 100 m above 1000 m and produce at most 62 dBA at 1 m. Weights range from 265 to 1450 kg. The document is a product summary and states that catalogue data may change without notice.

Key points

  1. Seven three-pole models: 100, 250, 400, 630, 800, 1000 and 1250 A; a 4-pole switched-neutral configuration is an option.
  2. Switching time at most 4 ms; at most 10 ms when source harmonic voltage exceeds 20%; at most 5 ms for 63 A versions.
  3. Rated voltage 208/380/400/415/440/480 Vac, tolerance plus or minus 10% (20% on request), frequency 50/60 Hz plus or minus 2 Hz (4 Hz on request).
  4. Switching phase angle 5 to 30 degrees; break-before-make, switching inhibited on downstream fault.
  5. Overload: 125% for 30 min, 150% for 10 min, 200% for 30 s, 2000% for 1 cycle, 4000% for half a cycle.
  6. AC/AC efficiency above 99%; load power factor 1 to 0.3; maximum crest factor 3:1.
  7. Weights 265, 290, 305, 615, 660, 1000 and 1450 kg; IP20, front access, top and bottom cable entry.
  8. Operating temperature 0 to 40 degrees C; 0.5% derating per 100 m above 1000 m; noise at most 62 dBA.
  9. Standards IEC EN 62310-1, -2, -3 and IEC EN 62947-3; CE and UKCA marking.

Using it in design

  • Choose one of the seven discrete models by load current and state the 4-pole switched-neutral requirement separately in the specification.
  • Where source harmonic content could exceed 20% THD, verify that the load tolerates the 10 ms transfer time.
  • Check in the system design that the phase-angle difference between the two sources stays within 5 to 30 degrees.
  • For high-altitude sites, apply the 0.5% per 100 m derating above 1000 m to the rated current.
  • Match the wall, back-to-back and side-by-side installation options and front access to the floor plan and service clearances.

Who should read it

Electrical designers selecting STS equipment for dual-fed critical loads and engineers preparing a product catalogue.

Document contents

  1. Product features and key options
  2. Applications
  3. STS technical data sheet: input, output, efficiency, general, environment, connectivity, regulations

Publication details

Authors
Ablerex
Publisher
Ablerex
Year
2024
Document number
Rev.2024/08
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Ablerex (2024). Ablerex STS technical data sheet Rev.2024/08. Ablerex. Rev.2024/08. https://ablerex.eu/wp-content/uploads/2024/04/BROCHURE_OEM-UPS_STS_LR.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.