Nitto Kogyo DS-MC Automatic Power Transfer Switch with Built-in Relay: Operating Instructions
Original title Nitto Kogyo DS-MC operating instructions B153130927
Nitto Kogyo
The Japanese operating instructions for Nitto Kogyo's DS-MC automatic power transfer switch with built-in relay: safety warnings, wiring, mounting clearances, transfer function and manual operation.
On this page
Overview
The manual presents the product as a two- or three-pole automatic transfer switch with an A source terminal (priority circuit), a B source terminal and a C load terminal. In the typical connection, the mains is on A and an emergency source on B. When mains fails the load transfers automatically from A to B, and back to A when mains returns; if both terminals are live, source A is selected. Standard transfer time is 10 to 200 ms and the transfer produces a distinct mechanical sound of about 85 dB.
The safety section states plainly that the product is not a circuit breaker and does not trip automatically on overcurrent. Installation and wiring must be done de-energized and by a qualified electrician; M6 terminal screws are tightened to 4.0 to 5.0 Nm. Other warnings include not exceeding rated voltage and current, not installing in high-temperature, humid, dusty, corrosive, vibrating or shock-prone environments, and not performing dielectric tests or insulation-resistance measurement between poles.
The mounting section gives surroundings clearances: if the side panel is metal, at least 4 mm in air and 6 mm creepage are required, and 10 mm must be left for cover opening. The permitted variation of rated operating voltage is 85% to 110%. The manual handle is for emergency use only and only after the circuit is de-energized; with the cover open the control mechanism stops, so the cover must be closed after manual operation. Supplied accessories are two terminal covers, one manual handle, screws and the manual.
Key points
- Terminals: A source (priority), B source and C load; 2-pole (2P) and 3-pole (3P) models.
- Automatic transfer from A to B on mains loss and back to A on return; if both terminals are live, A is selected.
- Standard transfer time 10 to 200 ms; about 85 dB of mechanical sound during transfer.
- The product is not a circuit breaker and does not trip automatically on overcurrent.
- Permitted variation of rated operating voltage is 85% to 110%.
- Tightening torque for M6 terminal screws is 4.0 to 5.0 Nm.
- Metal side panel: at least 4 mm in air and 6 mm creepage; 10 mm clearance for cover opening.
- The manual handle is used only in an emergency and with the circuit de-energized.
Using it in design
- Provide overcurrent and short-circuit protection independent of this switch, with separate protective devices on both source lines.
- Compare the 10 to 200 ms transfer time with the outage tolerance of downstream equipment; for loads that cannot tolerate it, place it behind a UPS or use it with an STS.
- In panel layout, keep 4 mm air and 6 mm creepage to adjacent metal surfaces and leave cover-opening clearance.
- Add the manual operating procedure, and keeping the manual near the product, to the operating instructions.
- Write the M6 terminal tightening torque (4.0 to 5.0 Nm) into the installation work instruction.
Who should read it
Electrical installation engineers and installers designing small-scale mains-to-generator transfer.
Document contents
- Safety precautions (installation and use)
- Outline and part names, circuit diagram
- Mounting dimensions and surrounding clearances
- Operating specification and power-source switching function
- Terminal cover fitting, manual operation, accessories
Publication details
- Authors
- Nitto Kogyo
- Publisher
- Nitto Kogyo
- Year
- 2026
- Document number
- B153130927
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Nitto Kogyo (2026). Nitto Kogyo DS-MC operating instructions B153130927. Nitto Kogyo. B153130927. https://ntec.nito.co.jp/svmn/data/09/B153130927.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
