Nitto Kogyo DS-MC integrated-relay automatic source changeover

Nitto Kogyo

Model table for Nitto Kogyo's DS-MC series automatic source changeover switch with built-in relay: 2- and 3-pole, 30 to 75 A, no external control circuit needed, and source A has priority.

On this page

Overview

The product page from Japanese manufacturer Nitto Kogyo presents the DS-MC series as an automatic source changeover switch with a built-in relay. Because the relay is inside the device, no external control circuit is needed; energising the main circuit is enough for switching to take place. The two sources connect to separate terminals, and when both are energised, source A is connected with priority.

The model table separates 2-pole and 3-pole versions. The 2-pole models are DS32MC (30 A) and DS62MC (60 A) with an operating voltage of AC 100 V. The 3-pole models are DS33MC (30 A), DS63MC (60 A) and DS73MC (75 A) with an operating voltage of AC 200 V. Switching current and power at the moment of changeover are given per group: 5.5 A and 550 W for the 2-pole 30 A group, and 4.7 A and 940 W for the 3-pole 30 A group.

The page stresses one key restriction: the device is not suitable for highly inductive loads. Price and delivery time are available from the manufacturer. The page offers an instruction manual link (B153130926) and drawing downloads. The document concerns a small-current switching product that provides automatic changeover between two mains supplies or mains and a generator, not a UPS.

For data-centre design, the product fits low-current auxiliary loads such as lighting, ventilation and small control panels that are fed automatically from two sources. It is not a substitute for large ATS solutions and represents the small-current end of its product family.

Key points

  1. Series: DS-MC, automatic source changeover switch with built-in relay; no external control circuit needed.
  2. Sources A and B have separate terminals; when both are live, source A is connected with priority.
  3. Models: DS32MC (2-pole, 30 A), DS62MC (2-pole, 60 A), DS33MC (3-pole, 30 A), DS63MC (3-pole, 60 A), DS73MC (3-pole, 75 A).
  4. Operating voltage: AC 100 V for 2-pole models and AC 200 V for 3-pole models.
  5. Switching current and power: 2-pole 30 A group 5.5 A and 550 W; 3-pole 30 A group 4.7 A and 940 W.
  6. Not suitable for highly inductive loads.

Using it in design

  • Select the 30, 60 or 75 A model step from the auxiliary load current, and set the pole count from the system voltage.
  • Check that the operating voltage (AC 100 V or AC 200 V) matches your source voltage.
  • Wire sources by priority so that the main supply is A and the standby is B (for example mains on A, generator on B).
  • Do not connect highly inductive loads such as motors and transformers behind this switch.

Who should read it

Electrical designers and panel builders selecting low-current automatic source changeover switches under Japanese standards.

Publication details

Authors
Nitto Kogyo
Publisher
Nitto Kogyo
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Nitto Kogyo Nitto Kogyo DS-MC integrated-relay automatic source changeover. Nitto Kogyo. https://ntec.nito.co.jp/content/ppreview.html?code=S11499

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.