Technical guideFree to read2015

PowerHub static transfer switch brochure

APECUS Technologies

This 2015 brochure from APECUS Technologies (Singapore) presents the single-phase PowerHub STS series, six models from 16 A to 100 A (3.5 kW to 22 kW); its specification table gives a transfer time of 6 ms or less and efficiency of 98% or more.

On this page

Overview

The four-page brochure describes the dual-input PowerHub static transfer switch (STS), which selects automatically between two independent AC sources. The user sets which input is the primary and which the backup; when the primary source fails, the unit moves the load to the second source on its own. The design relies on a two-stage switch under high-speed microcontroller control and prevents both inputs from feeding the load at once. The brochure dates from 2015 and reflects the product description that preceded the manufacturer's newer publications.

Transfer behaviour is explained for two cases, synchronous and asynchronous. If the phase error between the two sources lies within the preset range, they count as synchronised and the automatic transfer is immediate; sensing the condition may take a delay of no more than 5 ms. Manual transfer, manual retransfer and automatic retransfer take place with a delay of no more than 0.1 ms. If the sources are not synchronised, a 12 ms delay is inserted so that two unsynchronised sources are not short-circuited during the changeover. The same delay applies on the return from the alternative source to the preferred one.

The brochure carries two different transfer figures. The asynchronous description gives a 12 ms delay, while the features section claims a fastest transfer of 6 ms in the same phase and in different phases, and the specification table states 6 ms or less for every model. The connection diagrams show five source combinations: mains with mains, mains with UPS, UPS with UPS, mains with voltage stabiliser, and voltage stabiliser with UPS. Overcurrent protection acts when output current exceeds 110% and on inrush of 4 times.

The specification table covers the STS 16, 25, 32, 40, 63 and 100. Input and output voltage is 200 to 240 VAC, frequency 50 to 60 Hz, operating temperature 0 to 40 °C and humidity 10% to 90%. The chassis is 482 mm wide and 400 mm deep, at 1U or 3U height depending on model. Interfaces are RS232 and dry contact, with surge protection on both inputs and on the RS232 port. The brochure gives no three-phase models, no short-circuit withstand current and no measurement conditions for the transfer time.

Key points

  1. Six models: STS 16 (16 A, 3.5 kW), STS 25 (25 A, 5.5 kW), STS 32 (32 A, 7 kW), STS 40 (40 A, 8.8 kW), STS 63 (63 A, 13.8 kW), STS 100 (100 A, 22 kW).
  2. Input and output voltage 200 to 240 VAC ± 5 V, frequency 50 to 60 Hz; the series is single-phase.
  3. The specification table gives transfer time of 6 ms or less and efficiency of 98% or more.
  4. Synchronous transfer has a sensing delay of at most 5 ms; manual transfer and retransfer have a delay of at most 0.1 ms.
  5. Between unsynchronised sources, a 12 ms delay is added to both transfer and retransfer.
  6. The overcurrent threshold is 110%; protection types are overcurrent and short circuit.
  7. Chassis 482 x 400 mm at 1U or 3U depending on model; operating environment 0 to 40 °C and 10% to 90% humidity.
  8. Interfaces are RS232 and dry contact; the LCD shows electrical parameters, LEDs show status, and faults raise an audible alarm.

Using it in design

  • Record transfer time separately for the synchronous case (6 ms or less) and the asynchronous case (12 ms delay), and check load hold-up time against the asynchronous worst case.
  • Provide phase synchronisation between the two sources in the design (for example two UPS outputs); unsynchronised sources lengthen the transfer.
  • When choosing a model, compare load current with the rated current and the 110% overcurrent threshold, and assess server power-supply inrush against the 4 times limit.
  • Reserve 1U or 3U of height by model and 400 mm of depth in the rack layout, and check ambient temperature against the 40 °C limit.
  • Wire the RS232 and dry-contact outputs to the building management or monitoring system so source failures and transfers arrive as alarms.

Who should read it

Electrical engineers designing dual-source supplies for small computer rooms and at rack level, and procurement teams comparing STS products.

Document contents

  1. Static transfer switch: headline features
  2. Seamless power transfer without transferring your load
  3. Synchronous transfer
  4. Asynchronous transfer
  5. Different combinations of connecting methodology
  6. Product features
  7. PowerHub STS series technical specifications

Publication details

Authors
APECUS Technologies
Publisher
APECUS Technologies
Year
2015
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

APECUS Technologies (2015). PowerHub static transfer switch brochure. APECUS Technologies. https://www.apecus.com/wp-content/uploads/2023/12/PowerHub-Static-Transfer-Switch.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.