APECUS PowerHub static transfer switch current specifications

APECUS Technologies

The product page of APECUS Technologies lists four models of the PowerHub single-phase static transfer switch: STS 16, 25, 32 and 40 (16 A to 40 A, 3.5 kW to 8.8 kW), with transfer time of at most 6 ms, efficiency of at least 98%, and a 19-inch-wide 1U or 5U case.

On this page

Overview

The PowerHub STS manages the redundancy of a supply system made up of two independent sources so that the load receives a continuous output. One of the two inputs is preselected as the primary source and the other as backup; when the primary source fails, the switch moves the load to the backup source automatically. Source priority is user selectable. The page groups the features under six points: dual input static switch, wide power adaptability, transfer time of 6 ms or less, selectable priority of supply, overcurrent and lightning protection, and an RS232 and status output interface.

The brief specification table gives the four models in separate columns. The STS 16 is rated 16 A and 3.5 kW, the STS 25 25 A and 5.5 kW, the STS 32 32 A and 7 kW, and the STS 40 40 A and 8.8 kW. Voltage for both inputs and the output is 200 to 240 V AC (±5 V) and frequency 50 to 60 Hz. The overcurrent threshold is 110% and efficiency at least 98%. Operating temperature is 0 to 40 °C and relative humidity 10% to 90%. With these values the unit is designed for single-phase 230 V class in-rack loads.

Dimensions are given as width, depth and height: 482 x 400 mm and 1U for the STS 16 and STS 25, and 482 x 400 mm and 5U for the STS 32 and STS 40. The 16 A and 25 A models therefore take one rack unit, while the 32 A and 40 A models need five. The page gives no weight, short-circuit withstand, unsynchronised transfer behaviour or connection type; those data come from the technical specification document downloadable from the page or from the manufacturer. The current page lists four current ratings.

Key points

  1. Four models: STS 16 (16 A, 3.5 kW), STS 25 (25 A, 5.5 kW), STS 32 (32 A, 7 kW), STS 40 (40 A, 8.8 kW).
  2. Input and output voltage 200 to 240 V AC (±5 V), for both inputs; frequency 50 to 60 Hz.
  3. Transfer time at most 6 ms.
  4. Efficiency at least 98%; overcurrent threshold 110%.
  5. Dimensions (W x D x H): 482 x 400 mm x 1U for the STS 16 and STS 25; 482 x 400 mm x 5U for the STS 32 and STS 40.
  6. Operating temperature 0 to 40 °C; relative humidity 10% to 90%.
  7. Source priority is user selectable; an RS232 and status output interface is provided.

Using it in design

  • To connect single-corded rack devices to A and B feeds, pick the model current from the rack load: STS 16 up to 3.5 kW, STS 40 up to 8.8 kW.
  • Compare the 6 ms transfer time with the power supply hold-up time of the equipment fed.
  • In the rack layout, allow for the 5U height of the 32 A and 40 A models, the 400 mm depth and rear cable clearance.
  • Because of the 110% overcurrent threshold, keep the load below rated current and assess devices with high inrush separately.
  • Before specifying, ask the manufacturer for short-circuit withstand, connection type and the conditions on phase difference between the two sources.

Who should read it

Data-centre and network room engineers designing redundant in-rack supply and teams selecting rack-mount STS units.

Document contents

  1. Static Transfer Switch
  2. Features
  3. Brief Technical Specification

Publication details

Authors
APECUS Technologies
Publisher
APECUS Technologies
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

APECUS Technologies APECUS PowerHub static transfer switch current specifications. APECUS Technologies. https://apecus.com/product/static-transfer-switch

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.