Soltec ST-50/ST-100/ST-150 10U Static Transfer Switch Specifications
Original title Soltec ST-50/ST-100/ST-150 10U technical specifications
Soltec
Soltec's 10U rack-mount ST series static transfer switch comes in 50, 100 and 150 A ratings, with 1.5-3 ms transfer at 0 degrees phase difference, 3-6 ms below 90 degrees, and efficiency above 99%.
On this page
Overview
The product page presents the ST-50, ST-100 and ST-150 static transfer switches (STS), which move a load between two sources without interruption. The unit is 10U high, 440 x 440 x 550 mm (W x H x D), and weighs 24, 26 and 30 kg depending on model. It uses a break-before-make sequence, so the two sources are never connected at once.
Single or three phase is selectable, and rated voltage can be 120/208, 220/380, 230/400, 240/415 or 277/480 V. Input voltage tolerance is selectable at +/-5, 10, 15 or 20%, and frequency tolerance from +/-0.5 to +/-2.5 Hz. The phase difference limit between the two inputs is set at 5, 10, 15, 20 degrees or ignored. Sensitivity is low, medium or high, and transfer and return can be manual or automatic.
In the technical table, transfer time is 1.5-3 ms at 0 degrees difference and 3-6 ms below 90 degrees; the page's feature list quotes slightly different ranges (1.5-2 ms and 2-6 ms), so the table values should govern comparisons. Full-load efficiency is above 99%, cooling is by fan and noise is 50 dBA at 1 m. Operating altitude is below 2000 m with 5% derating per 1000 m. Safety is stated as EN 62310-1 and EMC as EN 62310-2.
Key points
- Three models: ST-50 (50 A), ST-100 (100 A), ST-150 (150 A); weights 24, 26, 30 kg.
- Enclosure is 10U rack, 440 x 440 x 550 mm (W x H x D).
- Rated voltage 120/208, 220/380, 230/400, 240/415 or 277/480 V; single or three phase.
- Transfer time is 1.5-3 ms at 0 degrees phase difference and 3-6 ms below 90 degrees (technical table).
- Input voltage tolerance +/-5/10/15/20% and frequency tolerance +/-0.5/1.0/1.5/2.0/2.5 Hz are selectable.
- The phase difference limit between inputs is selectable at 5, 10, 15, 20 degrees or ignored.
- Full-load efficiency above 99%; noise 50 dBA at 1 m; operating temperature 0-40 C.
- Altitude below 2000 m with 5% derating per 1000 m; standards EN 62310-1 and -2.
Using it in design
- When an STS serves single-corded loads in an A/B-fed row, compare its transfer time with the load's ride-through tolerance.
- Set the phase difference limit from the actual phase relationship of the two sources; with sources from different UPSs, synchronisation state decides the transfer time.
- Include the brief break from the break-before-make sequence in the load-side tolerance analysis.
- Write the maintenance scenario with interlocked manual bypass breakers into the operating procedure.
- Allow in the rack layout for 10U of space, 24-30 kg weight and fan noise.
Who should read it
Electrical engineers designing dual-source supply and data-centre designers selecting an STS for single-corded loads.
Document contents
- Features
- Specification table
- Brochure download
Publication details
- Authors
- Soltec
- Publisher
- Soltec
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Soltec Soltec ST-50/ST-100/ST-150 10U technical specifications. Soltec. http://soltec.com.tw/f/en_product_STS_ST50-ST150%20%2810U%29.asp
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.