Soltec STS50-STS1000 Static Transfer Switch Specifications

Original title Soltec STS50–STS1000 technical specifications

Soltec

Soltec's STS series static transfer switch comes in ten models from 50 to 1000 A, with transfer under 3 ms when sources are synchronised and under 6 ms when not, and efficiency above 99%.

On this page

Overview

The page presents ten STS models rated 50, 100, 120, 150, 200, 300, 400, 500, 800 and 1000 A. Input is 380/400/415 Vac three-phase with neutral, or 220/230/240 Vac single phase. Input voltage tolerance is selectable at +/-5/10/15/20% and frequency tolerance from +/-0.5 to +/-2.5 Hz; frequency is 50/60 Hz. The operating sequence is break-before-make (no source overlap) and a manual maintenance bypass is provided.

On source failure, transfer time is under 3 ms when S1/S2 are synchronised and under 6 ms when they are not; return time is stated as under 0.1 ms. The phase difference limit is selectable at 5, 10, 15, 20 degrees or ignored, and affects only return. Automatic or manual return and low/medium/high sensitivity can be set.

Efficiency at full load is above 99%. Noise is 52 or 55 dBA at 1 m. Ambient temperature is 0-40 C, storage -10 to +50 C, humidity 90% non-condensing and protection class IP20. Maximum installation altitude at rated power is 1000 m, with power reduced 1% per 100 m above that and a ceiling of 4000 m. Cabinets are 1600 x 550 x 800 mm, 1600 x 1100 x 800 mm or 1900 x 1100 x 800 mm (H x W x D), and weight for 380/400/415 V ranges from 180 to 450 kg.

Key points

  1. Ten models: STS50, 100, 120, 150, 200, 300, 400, 500, 800 and 1000 (rated current in A).
  2. Input 380/400/415 Vac three-phase with neutral or 220/230/240 Vac single phase; 50/60 Hz.
  3. Transfer on source failure: under 3 ms when S1/S2 are synchronised, under 6 ms when not; return time under 0.1 ms.
  4. Break-before-make sequence (no source overlap); manual maintenance bypass available.
  5. Phase difference limit 5/10/15/20 degrees or ignored; it affects return only.
  6. Full-load efficiency above 99%; noise 52 and 55 dBA at 1 m.
  7. Weight from 180 kg (STS50) to 450 kg (STS1000); cabinet height 1600 or 1900 mm.
  8. 1% power derating per 100 m above 1000 m, maximum 4000 m; IP20; standards EN 62310-1 and -2.

Using it in design

  • For single-corded loads on dual sources, select the STS rating against load current and inrush; the 50-1000 A range offers fine steps.
  • If the sources come from different UPSs, synchronisation state sets transfer time between 3 ms and 6 ms; verify the load's tolerance to that break.
  • Set the phase difference limit so that return does not occur across a large angle between sources.
  • The weight table covers only the 380/400/415 V configuration; confirm other voltages with the manufacturer.
  • At high-altitude sites, apply the derating above 1000 m.

Who should read it

Electrical engineers designing high-current dual-source supply and static transfer solutions.

Document contents

  1. Features
  2. Input
  3. Operating features
  4. Environmental
  5. Brochure download

Publication details

Authors
Soltec
Publisher
Soltec
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Soltec Soltec STS50–STS1000 technical specifications. Soltec. http://soltec.com.tw/f/en_product_STS_STS50-1000.asp

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.