ToneCooling TC-DCU-1600 Integrated Dry Cooling Unit (1600 kW)
Original title ToneCooling TC-DCU-1600 Integrated Dry Cooling Unit: Rev A
ToneCooling
ToneCooling's TC-DCU-1600 combines dry cooler, pumps and controls on one skid, rejecting 1600 kW at 30 °C inlet air and supplying primary-side liquid at 35 °C.
On this page
Overview
The document is the Rev A data sheet (18 September 2026) for Guangdong ToneCooling's TC-DCU-1600 integrated dry cooling unit (IDCU). The product combines an air-cooled heat exchanger, 1+1 circulation pumps, a control cabinet and a valve group on one base. It is installed outdoors horizontally and only piping and power are connected on site.
Rated capacity is 1600 kW at 30 °C inlet air. Air flow is 540,000 m³/h, liquid flow 4000 LPM and the coolant PG40 (40% propylene glycol/water). Liquid out/in temperature is 35 °C / 41.5 °C, air and liquid temperature gaps are 10 °C / 6.5 K, air pressure drop 120 Pa and liquid pressure drop below 1.5 bar. Pump head is 35 m.
On redundancy and control, fans are N+1 and pumps 1+1 with automatic switchover, with a dual-feed ATS. Fan MTBF exceeds 80,000 h. Fan speed (20-100%) and flow (40-100%) are regulated by PID against liquid temperature, with Modbus RTU and TCP/IP communication. Leak detection, IP55, DN200 flanges and a design pressure above 10 bar are listed.
The sheet positions the unit as primary-side heat rejection for liquid-cooled halls, replacing cooling towers and chillers; most of the year it runs on free cooling alone with no chiller and no makeup water. Ratings apply at 30 °C and PG40, with derating per the selection table for other ambient temperatures.
Key points
- Rated capacity 1600 kW (30 °C inlet air, PG40).
- Air flow 540,000 m³/h; liquid flow 4000 LPM.
- Liquid out/in 35 °C / 41.5 °C; air in/out 30 °C / 40 °C.
- Dimensions (W × D × H) 13300 × 2280 × 2535 mm; weight approx. 8500 kg.
- Power consumption below 90 kW; 3-phase 380 V 50/60 Hz or 480 V 60 Hz.
- Air pressure drop 120 Pa; liquid pressure drop below 1.5 bar; pump head 35 m.
- N+1 fans, 1+1 pumps with auto switchover, dual-feed ATS.
- Operating environment -30 to 45 °C, 5-90% RH; IP55.
Using it in design
- The rating point is 30 °C; read the capacity at the design ambient from the selection table derating and confirm the supply liquid temperature meets the liquid-cooled load requirement.
- PG40 on the primary side requires glycol viscosity and heat capacity corrections in secondary CDU heat exchanger and pump sizing.
- Assess N+1 fan and 1+1 pump redundancy against the whole-system redundancy target, including module count and ATS feeds.
- Check weight (8500 kg) and footprint (13300 × 2280 × 2535 mm) against roof or ground layout and air inlet clearances.
- Include the Modbus RTU/TCP register map in the BMS/DCIM integration scope.
Who should read it
Mechanical engineers designing primary-side heat rejection for liquid-cooled data halls.
Document contents
- Overview
- Key specifications
- Performance and control
- Monitoring, interfaces and environment
- Engineering fit
- Documents and factory tests
Publication details
- Authors
- ToneCooling
- Publisher
- ToneCooling
- Year
- 2026
- Document number
- TC-DS-DCU-1600, Rev A, 2026-09-18
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ToneCooling (2026). ToneCooling TC-DCU-1600 Integrated Dry Cooling Unit: Rev A. ToneCooling. TC-DS-DCU-1600, Rev A, 2026-09-18. https://tonecooling.com/wp-content/uploads/tonecooling-cdu-catalog/TC-DS-DCU-1600-EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.