Technical guideFree to read2026

ToneCooling TC-DCU-600 Integrated Dry Cooling Unit (600 kW)

Original title ToneCooling TC-DCU-600 Integrated Dry Cooling Unit: Rev A

ToneCooling

ToneCooling's TC-DCU-600 combines dry cooler, pumps and controls on one skid, rejecting 600 kW at 30 °C inlet air and supplying primary-side liquid at 35 °C.

On this page

Overview

The document is the Rev A data sheet (18 September 2026) for Guangdong ToneCooling's TC-DCU-600 integrated dry cooling unit (IDCU). The product combines an air-cooled heat exchanger, 1+1 circulation pumps, a control cabinet and a valve group on one base. It is installed outdoors horizontally and only piping and power are connected on site.

Rated capacity is 600 kW at 30 °C inlet air. Air flow is 240,000 m³/h, liquid flow 2000 LPM and the coolant PG40 (40% propylene glycol/water). Liquid out/in temperature is 35 °C / 40 °C, air and liquid temperature gaps are 10 °C / 5 K, air pressure drop 90 Pa and liquid pressure drop below 0.9 bar. Pump head is 35 m.

On redundancy and control, fans are N+1 and pumps 1+1 with automatic switchover, with a dual-feed ATS. Fan MTBF exceeds 80,000 h. Fan speed (20-100%) and flow (40-100%) are regulated by PID against liquid temperature, with Modbus RTU and TCP/IP communication. Leak detection, IP55, DN150 flanges and a design pressure above 10 bar are listed.

The sheet positions the unit as primary-side heat rejection for liquid-cooled halls, replacing cooling towers and chillers; most of the year it runs on free cooling alone with no chiller and no makeup water. Ratings apply at 30 °C and PG40, with derating per the selection table for other ambient temperatures.

Key points

  1. Rated capacity 600 kW (30 °C inlet air, PG40).
  2. Air flow 240,000 m³/h; liquid flow 2000 LPM.
  3. Liquid out/in 35 °C / 40 °C; air in/out 30 °C / 40 °C.
  4. Dimensions (W × D × H) 6600 × 2280 × 2535 mm; weight approx. 4500 kg.
  5. Power consumption below 43 kW; 3-phase 380 V 50/60 Hz or 480 V 60 Hz.
  6. Air pressure drop 90 Pa; liquid pressure drop below 0.9 bar; pump head 35 m.
  7. N+1 fans, 1+1 pumps with auto switchover, dual-feed ATS.
  8. Operating environment -30 to 45 °C, 5-90% RH; IP55.

Using it in design

  • The rating point is 30 °C; read the capacity at the design ambient from the selection table derating and confirm the supply liquid temperature meets the liquid-cooled load requirement.
  • PG40 on the primary side requires glycol viscosity and heat capacity corrections in secondary CDU heat exchanger and pump sizing.
  • Assess N+1 fan and 1+1 pump redundancy against the whole-system redundancy target, including module count and ATS feeds.
  • Check weight (4500 kg) and footprint (6600 × 2280 × 2535 mm) against roof or ground layout and air inlet clearances.
  • Include the Modbus RTU/TCP register map in the BMS/DCIM integration scope.

Who should read it

Mechanical engineers designing primary-side heat rejection for liquid-cooled data halls.

Document contents

  1. Overview
  2. Key specifications
  3. Performance and control
  4. Monitoring, interfaces and environment
  5. Engineering fit
  6. Documents and factory tests

Publication details

Authors
ToneCooling
Publisher
ToneCooling
Year
2026
Document number
TC-DS-DCU-600, Rev A, 2026-09-18
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ToneCooling (2026). ToneCooling TC-DCU-600 Integrated Dry Cooling Unit: Rev A. ToneCooling. TC-DS-DCU-600, Rev A, 2026-09-18. https://tonecooling.com/wp-content/uploads/tonecooling-cdu-catalog/TC-DS-DCU-600-EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.