Refra Galaxy chillers technical parameters, Galaxy Solo pp.10-11

Original title Refra Galaxy chillers technical parameters, Galaxy Solo pp.10–11

Refra

Refra's 2025 brochure gives air-cooled Galaxy Solo chillers on R290 propane at 48 to 125 kW capacity, EER 3.2 to 3.5 and 51 to 56 dB(A), rated at 35 °C ambient.

On this page

Overview

The document is the technical parameter brochure for the Galaxy air-cooled chiller range from Refra, built on natural refrigerants (R290 propane or propylene). The range has Mini (25 to 45 kW), Solo (45 to 120 kW) and two-circuit Twin (77 to 232 kW) families. This page focuses on the Galaxy Solo tables (GAL106, 108, 109, 110, 112, 113, 114).

Tables are for basic units without options. Capacity is rated at 35 °C outside air with 12/7 °C water and 35% ethylene glycol. Solo models are single-circuit, single-compressor units on 400 V 3-phase/N/PE. For each model the tables list power consumption, EER, SEPR, SEER, refrigerant charge, connection size, fan count and airflow, plate heat exchanger flow and pressure drop, dimensions and operating weight.

Standard equipment includes a Bitzer reciprocating compressor (Ex II-3G), microchannel air-cooled condenser, brazed plate evaporator, EC fans, a Siemens Climatix controller, an R290 leak detector and an emergency Ex fan. The frame is galvanized steel with 20 mm non-flammable PU foam insulation; 30 mm rock wool is offered for super-silent operation. A built-in hydraulic module, heat recovery and a buffer tank (500 or 800 L) are options.

The brochure is a product catalogue and contains no data-center-specific design guidance. It still supplies capacity, efficiency, sound and footprint data for selecting low-GWP chillers for mid-sized, auxiliary or telecom-room type cooling loads.

Key points

  1. Galaxy Solo capacity at 35 °C ambient, 12/7 °C water: GAL106 48.4 kW, GAL108 63.4 kW, GAL109 72.3 kW, GAL110 85.4 kW, GAL112 94.4 kW, GAL113 108.8 kW, GAL114 124.5 kW.
  2. EER ranges from 3.2 to 3.5; SEER from 5.38 to 5.69; SEPR from 6.50 to 7.04.
  3. Refrigerant is R290 (propane); charge ranges from 4.4 kg (GAL106 to 109) to 6.9 kg (GAL113 and 114).
  4. Sound pressure level at 10 m is 51 to 56 dB(A) (tolerance +/-2 dB(A)).
  5. Water flow ranges from 9.3 m³/h (GAL106) to 23.8 m³/h (GAL114); plate exchanger pressure drop 9.6 to 19.0 kPa; connections DN 50 to DN 80.
  6. Maximum current is 36.5 A (GAL106) to 107.7 A (GAL114) on 400 V 3-phase.
  7. Dimensions: GAL106 to 109 are 2607 x 1275 x 2355 mm at 980 to 1030 kg; GAL112 to 114 are 2877 x 2321 x 2355 mm at 1260 to 1290 kg.
  8. A buffer tank lengthens the unit and adds +290 to +430 kg for 500 L or +430 to +570 kg for 800 L, depending on model.
  9. The range carries the ATMO Approved label for its use of natural refrigerants.

Using it in design

  • Translate ratings to your design condition: the tables assume 35 °C ambient and 12/7 °C water; at higher ambient or warmer loops capacity and EER change, so request selection software output from the manufacturer.
  • R290 is flammable; check layout, ventilation and leak detection requirements against local regulation.
  • When choosing between single-circuit Solo and two-circuit Twin, weigh the need for circuit redundancy.
  • Carry plate exchanger pressure drop and DN connection size into pump and pipe selection.
  • Compare sound level, footprint and operating weight with roof or slab load limits and neighbour noise limits.

Who should read it

Mechanical designers and procurement engineers selecting air-cooled, low-GWP chillers for small and mid-sized cooling loads.

Document contents

  1. About Refra and the standard line
  2. ATMO Approved
  3. Galaxy Mini technical parameters
  4. Galaxy Solo description and technical parameters
  5. Galaxy Twin description and technical parameters

Publication details

Authors
Refra
Publisher
Refra
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Refra (2025). Refra Galaxy chillers technical parameters, Galaxy Solo pp.10–11. Refra. https://refra.eu/wp-content/uploads/2025/04/propane-chillers-standard-product-brochure-refra-1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.