Advanced Generator Modeling and Validation for Emerging AI Load Profiles

Rehlko · Majid Adeli (Rehlko)

A Rehlko G26-62 white paper on AI training load dynamics, reporting a generator model validated over 900 test-cell load steps with about 2% average deviation.

On this page

Overview

Rehlko's 2026 white paper G26-62 reviews power swings of AI training loads across compute and communication phases, their sub-synchronous frequency content and utility interconnection requirements. Utilities may set frequency-domain limits on load oscillation; an example band is 0.1-20 Hz, and measured AI load spectra can cluster around 0.2-3 Hz.

It then compares generator dynamic models: a simple model, Woodward DEGOV, IEEE GGOV1 and a modified GGOV1D, IEEE 421.5 excitation, SSFR-identified machine parameters and reduced-order models. The standard GGOV1 first-order actuator fails to reproduce the rebound-period frequency transients of diesel sets; a third-order actuator (GGOV1D) is proposed.

Validation is done in a test cell: load steps of 25-100% in 5% increments, 1-5 s durations, 10-50% idle base, 900 steps in total. No instability was seen and average model deviation was about 2%. The paper also summarises the 800 VDC power-block concept.

Key points

  1. Utilities may limit load oscillation in the frequency domain (example band 0.1-20 Hz); measured AI load spectra can cluster around 0.2-3 Hz.
  2. Oscillation risk bands: below 1 Hz inter-area modes, 1-2.5 Hz between nearby sources, about 7 Hz to over 100 Hz turbine-generator shaft torsional resonance.
  3. 800 VDC 17.5 MW power-block example: five 3.5 MW MV rectifiers (4+1) feeding 5000 A DC boards and 1500 A feeders.
  4. Validation: 25-100% load steps in 5% increments, 1-5 s durations, 10-50% idle base, 900 steps; no instability and about 2% average model deviation.
  5. The standard GGOV1 first-order actuator cannot reproduce diesel rebound-period frequency transients; a third-order GGOV1D is proposed.

Using it in design

  • For AI training loads, define the load spectrum (especially 0.2-3 Hz) and utility limits in the generator load-acceptance study.
  • Select the generator dynamic model on the basis of load-step validation; request the third-order actuator model rather than plain GGOV1 where needed.
  • Check torsional resonance bands in generator and prime-mover compatibility.
  • If an 800 VDC power block is considered, plan rectifier count and DC board currents together with redundancy.

Who should read it

Power-system engineers and modellers supplying AI loads from generators and microgrids.

Related standards

  • IEEE 421.5
  • ISO 8528-5
  • IEEE 1110

Publication details

Authors
Majid Adeli (Rehlko)
Publisher
Rehlko
Year
2026
Document number
G26-62
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor white paper; no open licence. Year from PDF metadata (Jul 2026).

Citation

Majid Adeli (Rehlko) (2026). Advanced Generator Modeling and Validation for Emerging AI Load Profiles. Rehlko. G26-62. https://techcomm.rehlko.com/techcomm/pdf/Rehlko_G26-62_Advanced_Generator_Modeling_and_Validation_for_Emerging_AI_Load-Profiles_WP.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.