Riedel Kooling Kool°M Series (R513A) Technical Data
Original title Riedel Kooling Kool°M Technical Data, 06/25, pp.2–4
Riedel Kooling
Riedel Kooling's Kool°M series comprises R513A air-cooled chillers from 8 to 200 kW, with net cooling capacity at 50 Hz of 9.7 kW to 180.3 kW.
On this page
Overview
Riedel Kooling, part of Glen Dimplex Precision Cooling, offers the Kool°M series as a modular platform for over 20 market segments, including medical, laser, machine tool and process cooling. The series was developed around low-GWP R513A and is said to meet the EU GWP limit of 750 for capacities above 12 kW from 2027 and the US limit of 700 from 2026.
The technical tables are split into three chassis groups: C1 (8-30 kW), C2/C3/C4 (30-100 kW) and C4 (100-200 kW). Net cooling capacity at 50 Hz is 9.7 kW for Kool°M 8 C1, 30.1 kW for 28 C1, 92.8 kW for 100 C4 and 180.3 kW for 200 C4. 60 Hz values are higher (for example 11.9 kW for Kool°M 8).
Capacity is given at a design point of 20 °C coolant outlet and 32 °C ambient, without counting pump capacity. Power consumption is defined with a 3 bar pump at the nominal point. Ambient range is -20 to +55 °C (standard version +5 to +45 °C), coolant outlet range -5 to +30 °C, and temperature stability ±2 K to ±0.5 K. Supply is dual-frequency 400 V/50 Hz and 460 V/60 Hz.
Units use electronic expansion valves, EC fans and microchannel condensers, and the series is stated to meet (EU) 2015/1095 and (EU) 2016/2281 efficiency standards. SEPR values range from 5.06 to 5.76. The document is process-cooling oriented; for data-centre work it serves as a reference for capacity, efficiency and temperature range.
Key points
- Series capacity 8-200 kW; refrigerant R513A.
- Net cooling capacity at 50 Hz: Kool°M 8 C1 9.7 kW, 12 C1 12.1 kW, 28 C1 30.1 kW, 100 C4 92.8 kW, 200 C4 180.3 kW.
- Nominal power consumption (50 Hz, 3 bar pump): 3.1 kW for Kool°M 8, 58.5 kW for Kool°M 200.
- Design point: coolant outlet 20 °C, ambient 32 °C; capacity excludes pump power.
- Ambient range -20/+55 °C (standard +5/+45 °C); coolant outlet -5/+30 °C.
- Temperature stability ±2 K, ±1 K or ±0.5 K.
- SEPR (2016/2281): 5.49 for Kool°M 8, 5.76 for 12, 5.06 for 80.
- Sound pressure at 5 m is 66-67 dB(A) in the groups listed.
Using it in design
- Compare capacity at the design point (20 °C water, 32 °C ambient); in hot climates correct with the manufacturer's curve as ambient rises.
- Since net capacity excludes pump power, add pump electricity separately.
- Choose the coolant outlet range and temperature stability class from the load requirement.
- Match the R513A choice to project requirements for the EU GWP limit of 750 (above 12 kW, from 2027).
- Take maximum current and fuse values into the supply panel calculation.
Who should read it
Mechanical designers selecting air-cooled chillers for data-centre and process cooling.
Document contents
- Kool°M series overview
- Technical data 8-30 kW, chassis C1
- Technical data 30-100 kW, chassis C2, C3, C4
- Technical data 100-200 kW, chassis C4
Publication details
- Authors
- Riedel Kooling
- Publisher
- Riedel Kooling
- Year
- 2025
- Document number
- 06/25
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Riedel Kooling (2025). Riedel Kooling Kool°M Technical Data, 06/25, pp.2–4. Riedel Kooling. 06/25. https://riedel-kooling.com/sites/g/files/emiian576/files/2025-07/250611-riedel-kooling-factsheet-koolm-C1-C4.4-en_1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.