IT Thermal Management Handbook
Rittal
Rittal's North American handbook describes its enclosure and in-row LCP cooling packages (DX and chilled water, up to 55-60 kW) with model tables and the case for open-loop and closed-loop cooling.
On this page
Overview
Rittal's IT Thermal Management Handbook (US493) approaches cooling for data centres, edge sites and enclosures from the manufacturer's side. The opening sections focus on heat-driven failure and downtime risk, on how hard businesses find it to quantify the cost of downtime, and on hot spots that cannot be managed simply by adding airflow as density grows. The proposed answer is localised closed-loop cooling, where hot and cold air stay inside the cabinet and the whole room need not be adjusted.
The edge section treats micro data centres in uncontrolled environments: fluctuating ambient temperature, scalability and rising power density are the three issues, answered by NEMA-rated enclosures, scalable in-row cooling, closed-loop solutions and the Blue e+ IoT interface. It notes that ASHRAE TC 9.9 guidance favours higher server inlet temperatures and that air-side and water-side economisation are spreading.
The open-loop section covers cooling compatible with the traditional cold-aisle and hot-aisle layout that evens out load differences between racks. Chilled water advantages are listed: EC fan technology, low air-side pressure loss, continuous control of chilled water flow, higher indirect free cooling at high water inlet temperature, modular fan units and fan modules that can be set up as N+1.
The product pages cover the LCP Rack DX, LCP Inline DX, LCP Rack CW and LCP Inline CW families. The technical table for LCP CW gives maximum output with the number of fan modules, dimensions, weight and water connection. The fan count delivered is separate from the count needed to reach maximum capacity, and the table shows this on separate rows.
Key points
- The downtime cost estimate quoted from IDC is 300 thousand to 1 million US dollars per hour.
- Cooling infrastructure accounts for 30-50% of data-centre energy cost (attributed to ASHRAE).
- LCP CW products give up to 55-60 kW on a 0.36 m² footprint (600 mm wide); IP 20 protection, RAL 9005 colour.
- LCP Rack CW (3311.238 and 3311.268) is 300 mm wide, 2000 mm high, 1200 mm deep; 10-60 kW with 1 to 6 fan modules required (1 or 4 supplied).
- LCP Rack CW shipping weight is 220 and 240 kg; maximum airflow 4800 and 8000 m³/h; water inlet temperature 59°F (15°C).
- LCP Inline CW (3311.148, .538, .548, .568) covers 18-60 kW; maximum operating pressure 6 bar; water connection 1½ inch BSP male thread.
- Fan modules are replaceable with the system running, without tools, and can be configured N+1; a 3-phase connection is standard for electrical redundancy.
- High water return temperatures (glycol variants) support heat recovery and heat-pump use.
Using it in design
- Keep the number of fan modules supplied separate from the number needed for maximum capacity; high load requires added fan modules and a redundancy check.
- Compare the water inlet temperature in the table (15°C) with the design chilled water temperature; a higher value raises the indirect free cooling share.
- For N+1 fan redundancy, plan one more fan module than the count shown in the capacity row.
- Check LCP dimensions (300 mm wide, 1050 or 1200 mm deep) and the flush or protruding installation in the bayed suite against the adjacent rack line-up.
- Carry the 1½ inch BSP thread and the 6 bar limit into the piping class.
Who should read it
Data-centre and edge designers selecting rack-level and in-row cooling, and mechanical and critical-infrastructure engineers.
Document contents
- Matching thermal management to the application challenge
- The challenges of data centers
- Cooling at the Edge
- ASHRAE and economization trends
- Supplement aisle containment with open loop cooling
- Closed loop cooling
- IT cooling solutions (LCP Rack and Inline, DX and CW)
- Accessories
- Technical data tables
- Service
Publication details
- Authors
- Rittal
- Publisher
- Rittal
- Year
- Year not stated
- Document number
- US493-BR-TR
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Rittal IT Thermal Management Handbook. Rittal. US493-BR-TR. https://www.rittal.com/us_en/apps/download/img/uploads/ITThermalManagementHandbook_US493-BR-TR_SingleWeb.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.