SK 3343.800 LCP Rear Door CW OCP (Rittal datasheet)
Original title SK 3343.800 LCP Rear Door CW OCP
Rittal
Rittal SK 3343.800 is an air/water heat exchanger rear door for Open Rack v3 giving up to 80 kW with 16 DC fans (N+1), 10-30 °C water inlet, 13,900 m³/h airflow and 47-56 VDC supply.
On this page
Overview
The document is the 17 November 2026 data sheet for Rittal's LCP Rear Door CW OCP, designed for OCP racks. The door is an air/water heat exchanger with 16 fans and a controller, mounted on the Open Rack v3 and optionally on other OCP-specified racks. It discharges server waste heat into the customer's own cold water circuit, and heat is carried directly to the chiller or free cooling unit.
Power comes from the DC busbar in the customer rack (47-56 VDC). The 16 DC axial fans are N+1 redundant. Fan control is based on the pressure difference between the servers and the heat exchanger, with temperature-difference control optional. The ambient air setpoint is regulated via a 2-way control valve (option). The controller can be replaced while operational and has a built-in display.
Technical values: maximum cooling output 80 kW, air volume 13,900 m³/h, usable height 44 OU, dimensions 570 × 2,264 × 258 mm (W × H × D), water connection G 1½" external thread, maximum permissible operating pressure 10 bar, water inlet temperature 10 to 30 °C and protection IP 10B. The cooling medium is saline and low-salinity water per VDI 2035 plus up to 50 volume percent glycol. The door opens to 135°.
For flexibility the customer chooses the hinge side and the water connection can be made from above or below thanks to the symmetrical layout. Components are replaceable while operational, a separate service door is provided and an emergency mode covers signal loss or component failure. The sheet does not state the air and water conditions at which capacity is measured.
Key points
- Maximum cooling output 80 kW; usable height 44 OU.
- Air volume 13,900 m³/h; 16 DC axial fans, N+1 redundant.
- DC supply 47-56 VDC from the rack busbar.
- Water inlet 10 to 30 °C; maximum operating pressure 10 bar; connection G 1½" external thread.
- Cooling medium: saline and low-salinity water per VDI 2035, up to 50 volume percent glycol.
- Dimensions 570 × 2,264 × 258 mm (W × H × D); door opening angle 135°.
- Protection IP 10B.
- Fan control is by server-to-exchanger pressure difference; temperature-difference control is optional.
- Controller and components can be replaced while operational.
Using it in design
- Have the manufacturer confirm loads up to 80 kW per rack against the 10-30 °C water inlet range and real water and air conditions; the sheet does not state them.
- Check the capacity of the OCP power architecture for 47-56 VDC supply from the rack busbar.
- Specify VDI 2035 water quality and the 50% glycol limit for the water circuit.
- Check door depth (258 mm) and 135° opening against aisle width and neighbouring rack spacing.
- Decide hinge side and top or bottom water connection in advance from pipe routing and rack row layout.
Who should read it
Mechanical engineers designing rear door cooling on OCP/Open Rack v3 racks.
Document contents
- Features and benefits
- Function principle
- Material and surface
- Technical data
Publication details
- Authors
- Rittal
- Publisher
- Rittal
- Year
- 2026
- Document number
- SK 3343.800
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Rittal (2026). SK 3343.800 LCP Rear Door CW OCP. Rittal. SK 3343.800. https://www.rittal.com/pdf-creator/variant/au-en/3343800
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
