Whitepaper - The Cooling Technology of the RiMatrix S Data Centre
Rittal
The paper explains how Rittal's standardised, modular RiMatrix S data centre pairs server modules (Single 6/9, Double 6/9) with cooling modules that blow cold air directly in front of the racks. A worked 60 kW example converts the PUE improvement into kWh and CO2.
On this page
Overview
Cooling modules come in 70 kW (Single 6 server module) and 100 kW (Single 9) classes. The air temperature difference over rack height is only about 1 K from U1 to U42. The paper also notes that battery service life benefits from about 20 C storage temperature.
Free cooling uses a dry cooler, and its share depends on water temperatures and climate. In the example climate, ambient exceeds 22 C for only 343 h, so free cooling is usable 96.1 % of the year. Differential-pressure (cross-section) control with closed-loop fans keeps cold-aisle overpressure at only 1-2 Pa, supplying just the air the servers draw.
Server fan energy rises sharply above about 27 C inlet when fans go to 100 % speed, which ties the inlet setpoint to fan power. For a 60 kW centre at 30 kW average load, PUE falls from 1.3 to 1.1 with optimised control, saving 50,510 kWh and 29,801 kg CO2 per year. It is a manufacturer paper and the calculation rests on a single example climate and load profile.
Key points
- Cooling modules come in 70 kW (Single 6) and 100 kW (Single 9) classes.
- Air temperature difference from U1 to U42 is only about 1 K.
- Delta-P control keeps cold-aisle overpressure at only 1-2 Pa.
- In the example climate ambient exceeds 22 C for only 343 h, so free cooling is usable 96.1 % of the year.
- Server fan energy rises sharply above about 27 C inlet as fans reach 100 % speed.
- 60 kW centre at 30 kW average load: PUE 1.3 to 1.1 saves 50,510 kWh and 29,801 kg CO2 per year.
- Battery life benefits from about 20 C storage temperature.
Using it in design
- In the free-cooling estimator compute economiser hours from hourly climate data against the required water supply temperature and report the percentage of the year.
- Show the relationship between inlet setpoint and server fan power and warn above 27 C.
- Support delta-P based fan control as an option with a 1-2 Pa target.
- Match cooling-module capacity to the selected server module’s demand in the prefabricated solution.
Who should read it
Designers evaluating modular data-centre cooling and free-cooling hours.
Related standards
- ASHRAE TC 9.9
- The Green Grid PUE
Publication details
- Authors
- Rittal
- Publisher
- Rittal
- Year
- 2015
- Document number
- 5_4358
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Rittal (2015). Whitepaper - The Cooling Technology of the RiMatrix S Data Centre. Rittal. 5_4358. https://www.rittal.com/imf/none/5_4358/Rittal_Whitepaper_The_Cooling_Technology_of_the_RiMatrix__5_4358/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.