SAER Solutions for Data Center: From air cooling to liquid and hybrid systems
Original title SAER Pumps and motors for data centers
SAER
SAER's January 2026 leaflet presents pump series for data centre cooling circuits, including SKD (4,500 m³/h, 210 m, up to 1,200 kW), NCB, L/LD, IR, MK and MG, with IE3-IE5 motor options.
On this page
Overview
The three-page leaflet presents the pump range of Italian manufacturer SAER for data centre cooling and water management (LEA 0269, January 2026). Applications are CRAH air cooling systems, direct-to-chip and immersion liquid cooling, dry coolers, chillers and heat exchangers, high-temperature loops, heat recovery, water treatment and distribution, fire fighting and utility water.
Headline values by series: SKD split-casing pumps up to 4,500 m³/h, 210 m head and 1,200 kW, water temperature -15/+120 °C (special -25/+150 °C); NCB/NCBK end-suction 2,300 m³/h, 129 m, 500 kW, -15/+90 °C; L and LD in-line 800 m³/h, 102 m, 90 kW, -25/+140 °C with most models above MEI 0.7; IR close-coupled 825 m³/h, 129 m, 110 kW; MK multistage 110 m³/h, 394 m, 55 kW; MG stub-shaft 825 m³/h, 129 m, 110 kW. All series are 50/60 Hz and can be mounted horizontally or vertically.
Common features include IE3, IE4 and IE5 efficiency class motors, cast iron, bronze, stainless steel and super duplex material options, motor monitoring and protection, internal and external protective coatings and inverter drive options. The manufacturer says hydraulic and electrical efficiency helps lower energy use, PUE and WUE and that impeller diameters are matched to system needs. High-temperature versions are suggested for return loops, heat recovery and high-temperature liquid cooling.
The document is a product introduction and carries no pump curves or efficiency values.
Key points
- SKD split-casing: 4,500 m³/h, 210 m, up to 1,200 kW; -15/+120 °C.
- NCB/NCBK end-suction: 2,300 m³/h, 129 m, 500 kW; -15/+90 °C.
- L and LD in-line: 800 m³/h, 102 m, 90 kW; -25/+140 °C; most models MEI above 0.7.
- IR close-coupled: 825 m³/h, 129 m, 110 kW.
- MK multistage: 110 m³/h, 394 m, 55 kW; compact vertical.
- MG stub-shaft: 825 m³/h, 129 m, 110 kW.
- Motor options IE3, IE4 and IE5; materials cast iron, bronze, stainless steel, super duplex.
- Horizontal or vertical mounting; 50/60 Hz.
- Applications: CRAH, direct-to-chip and immersion, dry coolers, chillers, heat recovery, water treatment, fire fighting.
Using it in design
- When selecting a pump, verify the operating point on the pump curve rather than the maximum flow and head; the leaflet gives only maximum values.
- For dry cooler and high-temperature liquid cooling loops, match the temperature limits (-15/+90 to +140/+150 °C) with operating temperature and glycol content.
- Define the IE3-IE5 motor class and the inverter option together with the variable-flow chilled water control strategy.
- In space-limited rooms use vertical mounting options (NCB, IR, MG, MK) to cut pump room footprint.
- Tie material and coating options to the water quality specification for corrosive or treated water circuits.
Who should read it
Mechanical designers selecting pumps for data centre cooling and water circuits.
Document contents
- Split casing pumps (SKD)
- End suction pumps (NCB/NCBK)
- In-line pumps single and twin head (L and LD)
- Close coupled pumps (IR)
- Multistage pumps (MK)
- Stub shaft pumps (MG)
- Applications
- Featuring
Publication details
- Authors
- SAER
- Publisher
- SAER
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
SAER (2026). SAER Pumps and motors for data centers. SAER. https://saerelettropompe.com/images/download-area/documenti-sito/LEA-Leaflet/LEA_0269_2026.01_Data-center_EN_00.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.