White paperFree to read2014

Facility Operations Maturity Model for Data Centers

Schneider Electric · Jennifer Schafer, Patrick Donovan

This 2014 Schneider Electric white paper introduces the Facility Operations Maturity Model (FOMM), a framework for grading a data center O&M program, patterned on the IT Governance Institute maturity structure.

On this page

Overview

FOMM groups 26 elements under 7 core disciplines; each element is divided into sub-elements, and every sub-element is scored from 1 (initial/ad hoc) to 5 (optimized) against defined criteria. The levels are Initial/ad hoc, Repeatable but intuitive, Defined process, Managed and measurable, and Optimized.

What separates the levels is spelled out: Level 3 requires documentation and formal training, Level 4 adds monitoring, continuous improvement and limited automated tools, and Level 5 requires integrated automation. Formal training means purpose-specific written materials combined with oral presentation, demonstration or hands-on practice plus a written evaluation.

Reporting examples include goal-versus-actual charts, a risk chart by line of inquiry and an effort-versus-impact ranking. Risk is reported across three lines of inquiry: formal process, awareness and training, and field implementation. Immediate corrective plans are advised for any element at 60% risk or above.

The first assessment is ideally made during commissioning for new sites, then repeated at regular intervals (perhaps annually) or after major changes in personnel, process, budget or goals. The paper also recommends an independent assessor.

Key points

  1. 26 elements under 7 disciplines, each divided into sub-elements.
  2. Sub-elements are scored 1-5: Initial, Repeatable, Defined, Managed, Optimized.
  3. Level 3 requires documentation and formal training.
  4. Level 4 adds monitoring, continuous improvement and limited automated tools; Level 5 requires integrated automation.
  5. Three lines of inquiry: formal process, awareness and training, field implementation.
  6. Immediate corrective plans advised for any element at 60% risk or above.
  7. First assessment during commissioning, then annually or after major change.

Using it in design

  • Assess operations and maintenance maturity across seven disciplines on a 1–5 scale per sub-element, comparing current and target levels.
  • Warn that design redundancy may not be realized when the design targets a high-criticality class but the assessment is missing or below Level 3 for change or emergency management.
  • Schedule the first assessment at commissioning and an annual reminder afterwards.
  • Flag every element at 60% risk or above for corrective action.

Who should read it

Owners and operations managers who want to measure operational maturity against design intent.

Related standards

  • EN 50600-3-1
  • Uptime Institute Tier Standard: Operational Sustainability

Publication details

Authors
Jennifer Schafer; Patrick Donovan
Publisher
Schneider Electric
Year
2014
Document number
WP 197
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Jennifer Schafer; Patrick Donovan (2014). Facility Operations Maturity Model for Data Centers. Schneider Electric. WP 197. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_PDON-96KPLV_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.