Why Cloud Computing is Requiring us to Rethink Resiliency at the Edge
Schneider Electric · Kevin Brown, Wendy Torell
A Schneider Electric white paper (WP 256, 2021, Revision 1) arguing that as applications move to the cloud, the few racks left at branch sites become more critical per rack, and ranking edge sites by downtime times severity.
On this page
Overview
The paper argues that as enterprise applications move to the cloud, the few on-premise racks left at branch sites become more critical per rack, because they host proprietary applications and the network path to the cloud. It contrasts the Tier III/IV practices typical of centralised and regional facilities with the Tier I reality of many local edge rooms: no security, cable clutter, 1N power, reliance on comfort cooling and no monitoring. Localized or micro data centers range from 1-2 MW down to 10-20 kW, trending toward a couple of racks in a room or closet.
From the user's point of view, series availability is dominated by the weakest edge site. In the example, a Tier III central site at 99.98% (1.6 h downtime) times a Tier I edge at 99.67% (28.8 h) gives 99.65%, or 30.7 hours of downtime. With ten Tier I edge sites of 100 people each plus one Tier III central site, 28,820 of the 30,400 people-hours of annual downtime come from the edge sites. The proposed scorecard multiplies annual downtime hours by a 1-5 severity rating based on people impacted and function, an FMECA-style method used to rank sites; a site at 98.60% availability (122.64 h/yr) with severity 5 scores 613.2, which is 65.5% of the overall 935.6.
Edge best practices are a locked room or enclosure with access control, 24x7 environmental and video monitoring, centralized or remote monitoring, redundant power paths, critical circuits on generator and a second network provider. The example of a Tier III micro data center is a prefabricated single 42U enclosure with redundant UPSs and power distribution. The paper offers a reliability method, but the scorecard rests on assigned severity ratings, and the record gives no more detail on how those ratings are set.
Key points
- Localized/micro data centers range from 1-2 MW down to 10-20 kW, trending to a couple of racks.
- Series availability: Tier III central 99.98% (1.6 h) x Tier I edge 99.67% (28.8 h) = 99.65%, or 30.7 hours of downtime.
- Ten Tier I edge sites of 100 people plus one Tier III central: 28,820 of 30,400 people-hours of downtime come from the edge.
- Scorecard: annual downtime hours x severity (1-5), an FMECA-style ranking.
- Example: 98.60% availability (122.64 h/yr) with severity 5 scores 613.2, 65.5% of 935.6.
- Typical edge room: no security, cable clutter, 1N power, comfort cooling, no monitoring.
- Example Tier III micro data center: prefabricated single 42U enclosure with redundant UPSs and power distribution.
- Best practices: locked access-controlled room, 24x7 monitoring, redundant power, generator-backed critical circuits, second network provider.
Using it in design
- Record availability or Tier targets, headcount served and severity from 1 to 5 across sites. Calculate series availability for dependent sites and prioritise by downtime times severity.
- Assess a single-42U micro data centre at 10–20 kW, including redundant UPS, dedicated cooling, a locked enclosure and environmental sensors.
- Warn when an edge room relies only on building comfort cooling, has 1N UPS at a high-severity site, lacks generator-backed circuits or has a single ISP.
- Flag open racks without access control.
Who should read it
IT managers and designers prioritising edge-room investments across many branch sites.
Related standards
- Uptime Institute Tier Standard: Topology
- ANSI/TIA-942
- EN 50600-1
- IEC 60812
Publication details
- Authors
- Kevin Brown; Wendy Torell
- Publisher
- Schneider Electric
- Year
- 2021
- Document number
- WP 256
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Kevin Brown; Wendy Torell (2021). Why Cloud Computing is Requiring us to Rethink Resiliency at the Edge. Schneider Electric. WP 256. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-AF3NSM_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.