Industry 4.0: Minimizing Downtime Risk with Resilient Edge Computing
Schneider Electric · Paul Lin, Steven Carlini
Schneider Electric WP 287 (2020) argues that Industry 4.0 technologies push compute to the plant floor, where edge IT in series with production means an IT outage stops the line.
On this page
Overview
IT "in series" with a process (e.g. F&B machines) means any IT outage immediately stops or degrades production, unlike "in parallel" applications with buffer time. Cited downtime costs: automotive average $22,000/min, up to $50,000/min (about $1.3M/h) (ATS 2005); IndustryWeek 2013 average $17,000 per incident; Aberdeen 2016 average $260,000/h, up 60% from $164,000 in 2014.
The paper compares a Tier 1 and a Tier 3 edge installation for an automotive plant: Tier 1 edge IT at 99.67% availability, 28.82 h/yr downtime and a $38.7M loss at $1.3M/h; Tier 3 at 99.98%, 1.58 h/yr and $3.4M, a 95% reduction ($35.3M/yr). Plant-floor challenges are harsh environment, limited space, open access, few IT staff and cyber exposure from IIoT.
Recommendations are purpose-built ruggedized or wall-mount enclosures; Li-ion UPS batteries on plant floors (life normally over 10 years, longer runtime for a given size, embedded monitoring, tolerance of temperatures above 40 °C); and redundant power and cooling for critical loads to achieve concurrent maintainability. Defence-in-depth cybersecurity takes six steps: security plan, network separation, perimeter protection, network segmentation, device hardening, monitoring and update. Pre-integrated edge solutions (WWT) cut field engineering cost 25-40%. Related frameworks are IEC 62443 and the Uptime Institute Tier Standard.
Key points
- Automotive downtime averages $22,000/min, up to $50,000/min (about $1.3M/h).
- Aberdeen 2016: $260,000/h, up 60% from $164,000 in 2014; IndustryWeek 2013: $17,000 per incident.
- Tier 1 edge IT: 99.67%, 28.82 h/yr, $38.7M loss.
- Tier 3 edge IT: 99.98%, 1.58 h/yr, $3.4M; 95% reduction ($35.3M/yr).
- In-series IT stops production immediately; in-parallel applications have buffer time.
- Li-ion UPS: life normally over 10 years, embedded monitoring, tolerance above 40 °C.
- Defence-in-depth in 6 steps: plan, separation, perimeter, segmentation, hardening, monitoring/update.
- Pre-integrated solutions cut field engineering 25-40% and maintenance 7%.
Using it in design
- Determine whether the edge site is coupled in series or in parallel with the process. For series coupling, assess the source’s Tier III-equivalent availability target, N+1 or 2N UPS/cooling and maintenance bypass.
- Convert availability into annual downtime hours and apply the hourly loss cost; compare Tier options using the Table 2 method.
- Record enclosure material, IP rating, double-wall construction and cable glands, plus UPS battery chemistry and maximum ambient temperature. Assess the source’s concern about VRLA above 40 °C.
- Checklist: firewall-equipped edge gateway, IT/OT network segmentation, DCIM/remote monitoring connectivity.
Who should read it
Designers and OT/IT owners putting edge IT on the plant floor and tying downtime cost to availability targets.
Related standards
- IEC 62443
- Uptime Institute Tier Standard: Topology
Publication details
- Authors
- Paul Lin; Steven Carlini
- Publisher
- Schneider Electric
- Year
- 2020
- Document number
- WP 287
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Paul Lin; Steven Carlini (2020). Industry 4.0: Minimizing Downtime Risk with Resilient Edge Computing. Schneider Electric. WP 287. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP287_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.