Properly Accounting for Scope 2 Emissions in the Age of Flexible Data Centers

Schneider Electric · Stuart Sheehan

A Schneider Electric white paper (WP 267, 2025) arguing that annual-average location-based Scope 2 accounting can misstate emissions as grids decarbonize and data centers operate flexibly, and why hourly or sub-hourly emission factors are needed.

On this page

Overview

The paper argues that annual-average location-based Scope 2 accounting misleads in two situations: when the grid decarbonizes, and when a data center can shift its load in time. An annual-average factor cannot tell whether load fell in a low-carbon hour or a high-carbon one. The author therefore proposes time-resolved accounting with hourly or sub-hourly emission factors.

In the example grid, the emission factor varies widely across hours: the lowest-decile hours are about 40% below the average and the highest-decile hours about 24% above it. That spread explains why shifting load toward cleaner hours changes real emissions while the annual average cannot see it. In the examples, annual-average and time-resolved estimates differ by up to about 15%.

The methodology section recommends 15-minute or hourly factors for flexible sites. Time-resolved accounting can reward load flexibility and can align carbon reduction with energy-cost reduction. The record shows percentages from one example grid, so the 15% and the 40%/24% figures should not be carried to other grids; they illustrate why the method is needed.

Key points

  1. Annual-average and time-resolved Scope 2 estimates can differ by up to about 15% in the examples.
  2. In the example grid, lowest-decile hours sit about 40% below the average emission factor.
  3. Highest-decile hours sit about 24% above the average.
  4. 15-minute or hourly emission factors are recommended for flexible sites.
  5. Load shifting creates real emission changes that annual averages do not show.
  6. Time-resolved accounting can reward flexibility and align carbon and energy-cost reduction.

Using it in design

  • Use an 8,760-hour emissions-factor profile where available, and identify calculations based on an annual average separately.
  • When BESS or workload shifting is modelled, compute Scope 2 hour by hour.
  • Show annual-average and time-resolved results side by side in the report.

Who should read it

Sustainability specialists doing carbon reporting and designers modelling flexible load and batteries.

Related standards

  • GHG Protocol Scope 2 Guidance

Publication details

Authors
Stuart Sheehan
Publisher
Schneider Electric
Year
2025
Document number
WP 267
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Stuart Sheehan (2025). Properly Accounting for Scope 2 Emissions in the Age of Flexible Data Centers. Schneider Electric. WP 267. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP267_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.