Research paperFree to read2023

Evaluation of Energy Efficiency of Data Centers

Original title Veri Merkezleri’nin Enerji Verimliliklerinin Değerlendirilmesi

Selçuk Üniversitesi · Rıdvan Çelik

A master's thesis accepted at Selcuk University in February 2023 calculates PUE and CUE for 18 data centres in Turkey: PUE values range from 1.19 to 2.78, with two above 2.5.

On this page

Overview

Rıdvan Çelik's master's thesis (Electrical-Electronics Engineering, advisor Assoc. Prof. Dr. Mehmet Akif Şahman, 46 pages) describes data-centre components and design considerations, then evaluates the energy efficiency of 18 data centres operating in Turkey. The centres are coded VM-1 to VM-18 for commercial reasons. The design part covers site selection, modularity, environmental control, electrical infrastructure, fire protection, security, computational fluid dynamics and thermal planning; it also covers green data centres, metrics and certificates, with examples from Apple, Google, Microsoft, Facebook and Equinix.

The method section introduces two metrics: PUE (total facility power over IT equipment power) and CUE (carbon usage effectiveness, total CO2 over IT equipment power). The text uses four PUE classes: 1.2-1.5 very efficient, 1.5-2 efficient, 2-2.5 average, above 2.5 inadequate. For each centre total facility power, IT equipment power, cooling capacity and an emission value (kgCO2/kWh) were collected; cooling capacity was not used in the calculations and is given for information only.

In the results, 6 centres are very efficient (VM-2, 3, 8, 10, 12, 15), 6 efficient, 4 average and 2 inadequate (VM-5 with PUE 2.67 and VM-14 with 2.78). The lowest calculated PUE is 1.19 (VM-15) and the highest 2.78 (VM-14). Most centres are in Istanbul, with examples from Bursa, Ankara and Izmir.

The methodological limit is important: in the input table total facility power is given in kVA for most centres and IT power in kW, and PUE is computed directly as the ratio of these two listed values; no common measurement basis (same unit, same period and measurement point) is defined. The results are therefore ratios between declared power values, not PUE from measured energy, and should be read as a method example, not a national efficiency benchmark. The thesis closes by recommending modular design, hot and cold aisle containment, free cooling, waste heat reuse, ultrasonic humidification and evaporative cooling.

Key points

  1. 18 Turkish data centres coded VM-1 to VM-18; total facility power is 1,000-4,550 kVA and IT equipment power 800-3,500 kW.
  2. Calculated PUE values range from 1.19 (VM-15) to 2.78 (VM-14); for example VM-1: 1.74, VM-2: 1.30, VM-5: 2.67.
  3. Classification by PUE: very efficient 1.2-1.5 (6 centres), efficient 1.5-2 (6), average 2-2.5 (4), inadequate above 2.5 (2: VM-5 and VM-14).
  4. CUE values are calculated between 2.1E-04 and 5.4E-04 (emission values of 0.25-0.745 kgCO2/kWh).
  5. PUE is total facility power over IT equipment power; CUE is total CO2 over IT equipment power, so CUE has units while PUE is dimensionless.
  6. The thesis cites an industry average PUE of 2.5-3 in older studies and about 1.7 in newer ones, and about 2.0 for an average US data centre.
  7. Method limit: the input table mixes kVA and kW, and PUE is the ratio of listed values without a defined common measurement basis.
  8. Recommendations: modular data centre, hot and cold aisle containment (hot aisle containment more effective but harder to implement), free cooling, waste heat recovery, ultrasonic humidification (90% less energy than conventional methods), evaporative cooling.

Using it in design

  • In PUE calculation, define numerator and denominator in the same unit (kW) and for the same measurement period as measured energy (kWh); dividing a kVA rating by kW IT power does not give PUE.
  • Read the PUE distribution of existing Turkish facilities (1.19-2.78) only as a method example; set your own target PUE from measured data using the ISO/IEC 30134-2 method.
  • For carbon performance, report CUE together with PUE and take the emission factor from the current official annual factor.
  • In new designs, evaluate hot and cold aisle containment, free cooling and heat-reuse options at concept stage, noting that site selection is critical for free cooling.
  • Treat modular and flexible construction as a design principle for capacity growth and energy efficiency.

Who should read it

Engineers designing or operating data centres in Turkey, students studying energy-efficiency assessment methods, and teams wanting an example of PUE and CUE calculation.

Document contents

  1. 1. Introduction
  2. 2. Literature review
  3. 3. Data centres (general structure, requirements, availability, design considerations, green data centres)
  4. 4. Data centre examples (in Turkey and worldwide)
  5. 5. Materials and methods (energy efficiency metrics: PUE, CUE; efficiency calculations)
  6. 6. Results and recommendations

Publication details

Authors
Rıdvan Çelik
Publisher
Selçuk Üniversitesi
Year
2023
Document number
Yüksek lisans tezi, Elektrik-Elektronik Mühendisliği, Şubat 2023
Document language
Turkish
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher or university publicly accessible text; no open redistribution licence established. Source-method limitations explicitly retained. Does not close the measured annual Turkish PUE data gap.

Citation

Rıdvan Çelik (2023). Veri Merkezleri’nin Enerji Verimliliklerinin Değerlendirilmesi. Selçuk Üniversitesi. Yüksek lisans tezi, Elektrik-Elektronik Mühendisliği, Şubat 2023. https://acikerisim.selcuk.edu.tr/server/api/core/bitstreams/662d31d9-d132-49c7-944b-67681bac7460/content

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.