SENHO CRA Series Air Cooled Central Chillers (76-986 kW)

Original title SENHO CRA air-cooled central chillers, specification tables

SENHO

The SENHO CRA series are air-cooled central chillers with screw compressors and R407C, covering 76 to 820 kW at 50 Hz (91 to 986 kW at 60 Hz) with 45 °C maximum ambient.

On this page

Overview

The page presents SENHO's CRA series of air-cooled central chillers. The general information gives a cooling capacity range of 76-986 kW, maximum working ambient of 45 °C, temperature control range of 5 to 30 °C, an air-cooled condenser, screw compressors and R407C refrigerant.

Standard components are Hanbell or Bitzer semi-hermetic twin-screw compressors (a Danfoss or Copeland scroll version exists below 400 kW), a Siemens PLC with touch screen, Schneider electrical parts, an epoxy-coated hydrophilic aluminium-fin condenser, a shell-and-tube evaporator and efficient axial fans. Options are a variable frequency drive (VFD) version, enlarged condensers or R134a for high ambient, a low-ambient kit down to -40 °C, a food-grade water circuit and a factory-integrated pump and tank.

The specification table covers 14 single-compressor models (CRA030W1 to CRA250W1; 76-695 kW at 50 Hz) and 8 double-compressor models (CRA100W2 to CRA300W2; 274-820 kW at 50 Hz) with capacity, total power, compressor and condenser power, condenser air volume, chilled-water flow, pipe size, dimensions and weight.

Power values assume a 3-phase 400 V 50 Hz supply; water flow is a nominal design value at 5 °C Delta-T and actual flow depends on pump performance and site piping. The page is oriented to industrial process cooling; for data-centre chiller selection the temperature regime and redundancy need separate evaluation.

Key points

  1. Capacity range 76-986 kW (76-820 kW at 50 Hz); maximum ambient 45 °C; control range 5-30 °C.
  2. Single-compressor CRA030W1-250W1: 76, 105, 137, 150, 200, 232, 273, 320, 388, 405, 448, 490, 593, 695 kW (50 Hz).
  3. Double-compressor CRA100W2-300W2: 274, 296, 394, 490, 546, 640, 784, 820 kW (50 Hz).
  4. CRA030W1: total power 30.2 kW, chilled-water flow 13 m³/h, 3 in pipe, 1,150 kg; CRA250W1: 229.7 kW, 119 m³/h, 8 in, 6,000 kg.
  5. CRA300W2: total power 273.6 kW, 141 m³/h, 6 in, 6,500 kg (double compressor).
  6. Water flow is calculated at 5 °C Delta-T; power figures are for 400 V / 3 phase / 50 Hz.
  7. R407C; Hanbell or Bitzer screw compressors; Siemens PLC; epoxy-coated condenser.
  8. Options: VFD version, -40 °C low-ambient kit, R134a high-ambient kit, integrated pump and tank.

Using it in design

  • When selecting a chiller for a data centre, compare the 5-30 °C control range with the operating water temperature regime; flow is based on 5 °C Delta-T, so recalculate flow for a wider Delta-T.
  • A 45 °C maximum ambient does not guarantee capacity is maintained in hot climates; obtain the capacity correction for the site design temperature from the manufacturer.
  • Carry weights (1,150-6,500 kg) and dimensions, with the 50 Hz capacities, into the roof or ground load calculation.
  • For N+1 redundancy, compare several chillers against double-compressor models.
  • Specify the integrated pump and tank package separately, with BMS integration and backup power.

Who should read it

Mechanical designers and procurement engineers selecting air-cooled central chillers.

Document contents

  1. General information
  2. Standard features and components
  3. Available options
  4. Specification table (single and double compressor)
  5. Related products

Publication details

Authors
SENHO
Publisher
SENHO
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

SENHO SENHO CRA air-cooled central chillers, specification tables. SENHO. https://senho-chiller.com/industrial-chillers/air-cooled-central-chillers/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.