Thermodynamic Analysis of Waste Heat Source Industrial Heat Pumps
Original title Atık Isı Kaynaklı Endüstriyel Isı Pompalarının Termodinamik Analizi
Uluslararası Sürdürülebilir Mühendislik ve Teknoloji Dergisi · Sinem Sezgin, Reşat Selbaş
A 2026 paper in the International Journal of Sustainable Engineering and Technology analyses a heat pump making 55-58 degrees C hot water from 30 degrees C waste heat; COP peaks at 4.52 with R1234ze(Z) and is 4.14 with R245fa.
On this page
Overview
The paper treats recovery of low-temperature industrial waste heat in terms of energy efficiency and environmental impact. A single-stage vapour compression heat pump using 30 degrees C waste heat is modelled theoretically to heat a factory's administrative unit with 55-58 degrees C hot water. The components are compressor, condenser, expansion valve and evaporator; the waste heat source is return water entering the evaporator at 1000 kg/h, 30 degrees C and 3 bar.
Mass, energy and exergy balances are written for each component, with ambient conditions of 298.15 K and 101.325 kPa. Four refrigerants are compared: R1234ze(Z) (A2L, GWP 7), R245fa (B1, GWP 1030), R1233zd(E) (A1, GWP 4.5) and R123 (B1, GWP 77, ODP 0.02). Performance is assessed for different evaporator and condenser temperatures and compressor efficiencies. At about 30 kW condenser heat load, COP lies between 4.14 and 4.52: R1234ze(Z) 4.52, R1233zd(E) 4.48, R123 4.24 and R245fa 4.14. The highest exergy efficiency is about 0.43 for R1234ze(Z). Total exergy destruction is 4.571 kW for R1234ze(Z) and 5.308 kW for R245fa, concentrated in the evaporator and compressor.
The author notes that COP and exergy efficiency rise as evaporator temperature increases and condenser temperature falls, but in practice both are limited by source temperature and required outlet temperature. The study is theoretical; pressure losses and heat losses to the environment are neglected and results need confirmation by an experimental prototype or field measurement. It does not address data centre waste heat directly, but gives refrigerant selection and exergy data for heat pumps lifting low-temperature waste heat to hot water.
Key points
- The system makes 55-58 degrees C hot water from a 30 degrees C waste heat source, with source and heating water flows of 1000 kg/h.
- At about 30 kW condenser heat load, COP lies between 4.14 and 4.52.
- COP ranking: R1234ze(Z) 4.52, R1233zd(E) 4.48, R123 4.24, R245fa 4.14.
- The highest exergy efficiency is about 0.43 for R1234ze(Z).
- Total exergy destruction is 4.571 kW for R1234ze(Z), 4.648 kW for R1233zd(E), 5.064 kW for R123 and 5.308 kW for R245fa.
- Exergy destruction is largest in the evaporator (finite temperature difference) and the compressor (non-isentropic compression).
- GWP values: R1234ze(Z) 7, R1233zd(E) 4.5, R123 77, R245fa 1030; safety classes A2L, A1, B1, B1.
- R1234ze(Z) as an A2L fluid requires leak detection, ventilation and electrical safety measures; R1233zd(E) with class A1 is easier in operating safety.
- The study is theoretical; pressure and heat losses are neglected.
Using it in design
- In a waste heat recovery heat pump, choose the refrigerant not on COP alone but with GWP, safety class, availability and compressor compatibility.
- If an A2L fluid is chosen, add leak detection, ventilation and electrical safety measures for the plant room to the project.
- COP rises as source temperature rises and heating water temperature falls; optimise source-sink temperature match and heat exchanger approach temperature.
- Reduce exergy destruction by improving evaporator area, approach temperature and compressor efficiency together.
- Tie theoretical results to an economic analysis with part-load behaviour, annual operating hours and energy prices in field design.
Who should read it
Mechanical engineers designing waste heat recovery and heat pumps, and researchers selecting refrigerants.
Document contents
- Introduction
- Material and Method
- System description
- Research Findings
- Results and Discussion
- References
Publication details
- Authors
- Sinem Sezgin; Reşat Selbaş
- Publisher
- Uluslararası Sürdürülebilir Mühendislik ve Teknoloji Dergisi
- Year
- 2026
- Document number
- 10(1), 15–25
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. Publisher page DOI ends 1892391; PDF headers incorrectly show 18923911. Publisher DOI retained with discrepancy recorded. Refrigerant property tables and classifications were not independently verified or imported.
Citation
Sinem Sezgin; Reşat Selbaş (2026). Atık Isı Kaynaklı Endüstriyel Isı Pompalarının Termodinamik Analizi. Uluslararası Sürdürülebilir Mühendislik ve Teknoloji Dergisi. 10(1), 15–25. https://doi.org/10.62301/usmtd.1892391
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.