Shimge BL(T) 50 Hz catalogue, hosted by Dai Ly May Bom
Shimge
The Shimge BL(T) catalogue gives performance tables, motor power, temperature limits and an NPSH method for stainless steel vertical multistage pumps rated from 2 to 200 m³/h.
On this page
Overview
The catalogue presents the BL(T) series as a high-efficiency, low-noise, non-self-priming vertical multistage stainless steel centrifugal pump. The standard motor is a fully enclosed two-pole unit with IP55 protection and class F insulation. The mechanical seal is balanced and cartridge type, with hard-metal dynamic and fluorine-rubber static sealing.
Application limits: single-phase 220 V-50 Hz or three-phase 220/380 V-50 Hz supply, liquid temperature 0 to 68°C for the normal type and 0 to 120°C for the hot-water (BLT) type, ambient -15 to +40°C and pH 5 to 8. A larger motor is advised when density or viscosity exceeds that of water. Above 40°C ambient or 1000 m altitude cooling weakens, so motor output P2 falls and a bigger motor should be chosen.
The selection section lists duty point, pipework losses, NPSH and efficiency. Minimum inlet pressure is calculated as H = pb x 10.2 - NPSH - Hf - Hv - Hs, with the safety margin Hs typically 0.5 m. The model code BL(T) 32-2-2-16 encodes rated flow, number of stages, number of small impellers and material.
Model tables cover BL(T)2, 4, 8, 12, 16, 20, 32, 45, 64, 90, 120, 150 and 200, with flow range (for example 1-3.5 m³/h for BL(T)2 and 100-240 m³/h for BL(T)200), motor power range (0.37-3 kW up to 18.5-110 kW) and flow-head points for each stage count. These points are not duty points selected for a particular plant.
Key points
- Models run from BL(T)2 to BL(T)200 with rated flow of 2 to 200 m³/h.
- Flow range is 1-3.5 m³/h for BL(T)2 and 100-240 m³/h for BL(T)200.
- Motor power range is 0.37-3 kW for BL(T)2 and 18.5-110 kW for BL(T)200.
- Motor is IP55, insulation class F, two-pole; 50 Hz single-phase 220 V or three-phase 220/380 V.
- Liquid temperature is 0-68°C for the normal type and 0-120°C for BLT hot-water; ambient -15 to +40°C; pH 5-8.
- Above 40°C ambient or 1000 m altitude, motor output (P2) drops and a larger motor is needed.
- The minimum inlet pressure formula typically uses a 0.5 m safety margin.
- The BLT hot-water series is listed separately; material variants are not repeated as separate model rows.
Using it in design
- For cooling-water and glycol circuits, compare liquid temperature and pH with the catalogue limits (0-68°C normal, 0-120°C BLT, pH 5-8).
- Select the pump at the intersection of system and pump curves and near best efficiency, not at a single table point.
- In suction calculations combine NPSH, pipe loss, vapour pressure and the 0.5 m margin, especially for hot water and long suction lines.
- Do not stop at the table motor rating; apply derating above 40°C ambient or 1000 m altitude.
- Do not read motor rating as measured power; use hydraulic and motor efficiency at the duty point for energy calculations.
Who should read it
Mechanical designers selecting vertical multistage pumps for cooling water, pressure boosting and process circuits.
Document contents
- Product features
- Model instruction
- Application limits and applications
- Calculation of minimum inlet pressure
- Selection of pumps
- Mechanical seal configuration
- Maximum ambient temperature and performance range
- Performance curves and tables BL(T)2 to BL(T)200
- Dimensions
Publication details
- Authors
- Shimge
- Publisher
- Shimge
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.