Technical guideFree to readYear not stated

Shuangliang Absorption Chiller Product Catalogue, printed pp.34-35, 0.6 MPa SI table

Original title Shuangliang Absorption Chiller Product Catalogue, printed pp.34–35, 0.6 MPa SI table

Shuangliang

The Shuangliang catalogue covers steam, hot-water, flue-gas and direct-fired LiBr absorption chillers; the steam-fired ST-H2 series spans 350 to 11630 kW at a COP of 1.41.

On this page

Overview

The catalogue covers Shuangliang's flue-gas, direct-fired, steam-operated double- and single-effect and hot-water-operated lithium bromide (LiBr) absorption chillers and heat pumps. The manufacturer says it built its first LiBr absorption chiller in 1985, helped draft the Chinese national standard in 1992 and listed on the stock exchange in 2003. It notes that waste heat, solar and geothermal energy can also drive the machines.

Technical tables are given for each type. For the steam-operated double-effect ST-H2 series, the 0.6 MPa(G) steam table runs from ST-99H2 (350 kW, 99 USRt) to ST-3307H2 (11630 kW, 3307 USRt). Nominal conditions are 12/7°C chilled water, 32/38°C cooling water and a scale factor of 0.086 m²K/kW.

For each model the tables list chilled and cooling water flow and pressure loss, connection sizes, steam consumption, steam and condensate pipe sizes, electric power and current, dimensions, and operating and shipping weight. For example ST-99H2 shows steam consumption of 376 kg/h, electric power of 3.8 kW and operating weight of 6.5 t; for ST-3307H2 these are 12530 kg/h, 26.4 kW and 103 t.

The notes state a COP of 1.41 in the 0.6 MPa table (steam consumption 12.35 kg/(10^4 kcal/h)) and 1.43 in the 0.8 MPa table at 30/36°C cooling water; capacity adjustable from 20 to 100% and chilled water flow from 60 to 120%; lowest chilled water outlet 5°C; condensate below 90°C at under 0.05 MPa(G) back pressure. Inconsistencies in the weight column headings mean weights need confirmation.

Key points

  1. The ST-H2 steam-fired double-effect series covers 350 kW (99 USRt) to 11630 kW (3307 USRt) in the 0.6 MPa(G) table.
  2. Nominal condition: chilled water 12/7°C, cooling water 32/38°C, scale factor 0.086 m2K/kW.
  3. COP is 1.41 (0.6 MPa) and 1.43 (0.8 MPa) at 30/36°C cooling water.
  4. Steam consumption is 376 kg/h for ST-99H2 and 12530 kg/h for ST-3307H2.
  5. Electric power is 3.8 kW for ST-99H2 and 26.4 kW for ST-3307H2; supply 3-phase 380 V 50 Hz.
  6. Capacity is adjustable 20-100% and chilled water flow 60-120%.
  7. Lowest chilled water outlet is 5°C; condensate below 90°C and back pressure below 0.05 MPa(G).
  8. Operating weight runs from 6.5 t (ST-99H2) to 103 t (ST-3307H2).

Using it in design

  • Consider an absorption chiller as an alternative to electric compressor chillers where waste heat or steam is available; note the COP of 1.41 and the large heat rejection.
  • Size the cooling tower and condenser water pump for the larger heat rejection of absorption machines; the table lists 86 m3/h of cooling water for ST-99H2.
  • Match steam pressure (0.4, 0.6 and 0.8 MPa tables), condensate return and steam pipe size to the plant steam source.
  • Use manufacturer-confirmed values for weight and foundation calculations, since the catalogue weight headings are inconsistent.
  • Compare the 20-100% part-load range and the 5°C minimum chilled water outlet with the data-centre system design.

Who should read it

Mechanical designers of power plants, CHP and data centres evaluating heat-driven cooling.

Document contents

  1. Flue Gas Type LiBr Absorption Chiller/Heater
  2. H2 Type Direct Fired LiBr Absorption Chiller/Heater
  3. Steam-Operated Double Effect LiBr Absorption Chiller
  4. Steam-Operated Single Effect LiBr Absorption Chiller
  5. Hot Water Operated Two Stage LiBr Absorption Chiller
  6. Table of Technical Parameters (0.6 MPa) (SI)

Publication details

Authors
Shuangliang
Publisher
Shuangliang
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Shuangliang Shuangliang Absorption Chiller Product Catalogue, printed pp.34–35, 0.6 MPa SI table. Shuangliang. https://shuangliang.ru/upload/iblock/58b/shuangliang_katalog.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.