SENTRON Miniature Circuit Breakers Technology
Siemens
A Siemens manufacturer primer identifying IEC 60898-1 magnetic trip-characteristic envelopes; the class bounds are screening inputs, not pair-specific selectivity evidence.
On this page
Overview
This document is Siemens's 2016 manufacturer primer on SENTRON miniature circuit breakers (MCBs). The primer identifies the magnetic trip-characteristic envelopes according to IEC 60898-1. It is under Siemens copyright; this record rests only on metadata and a short summary, not on the primer as a whole. As a manufacturer introduction, it is a reference that presents the technology of a product family rather than a general design rule.
The key information in the record is the broad magnetic operating envelopes for the referenced AC classes: class B at 3 to 5 times rated current, class C at 5 to 10 times and class D at 10 to 20 times. These ranges are broad class bounds showing at which current multiples the instantaneous (magnetic) trip region of an MCB begins under short-circuit conditions. The information is taken from the 'Tripping characteristics' section.
An important limit applies: these broad class bounds are screening inputs and do not prove the selectivity of a specific pair of devices. Real selectivity verification must be done with the manufacturers' selectivity tables or trip curves for the devices concerned, together with the short-circuit current. In short, this document is useful for quickly recalling typical magnetic trip multiples of MCB classes, but it cannot be the sole basis of a protection-coordination decision.
Key points
- The source is Siemens's 2016 SENTRON MCB manufacturer primer.
- It identifies IEC 60898-1 magnetic trip-characteristic envelopes.
- For the referenced AC classes the broad magnetic operating envelope for class B is 3-5 times rated current.
- Class C: 5-10 times rated current.
- Class D: 10-20 times rated current.
- These broad class bounds are screen inputs, not pair-specific selectivity evidence.
Using it in design
- Use the broad class bounds (B 3-5, C 5-10, D 10-20 times) as screening inputs in a selectivity study.
- Verify selectivity claims for specific device pairs with manufacturer selectivity tables or trip curves.
- State in reports that class envelopes are not pair-specific selectivity evidence.
Who should read it
Electrical designers doing low-voltage protection and selectivity studies and engineers selecting MCB classes.
Publication details
- Authors
- Siemens
- Publisher
- Siemens
- Year
- 2016
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation