SIVACON S8: Technical Planning Information (status 01/2025 V3-korr)
Original title SIVACON S8: Technical Planning Information
Siemens
A planning manual of 143 pages from Siemens for the SIVACON S8 low-voltage switchboard system up to 7,000 A, covering configurations, mounting designs, reactive power compensation, communication, dimensions, weights and losses, and IEC 61439-2 design verification.
On this page
Overview
The manual presents SIVACON S8 as a modular low-voltage system, design verified by testing to IEC 61439-2, used as a power distribution board and motor control centre up to 7,000 A. Three principles stand out: safety, cost-efficiency from the start and flexibility through modularity. Siemens SIMARIS tools (SIMARIS design for network calculation, project for space requirements and 3D model for BIM, curves for tripping characteristics, configuration and control) support dimensioning. The document carries publication status 01/2025; the hosted file name says February 2025, but the document's imprint gives 01/2025.
The technical data table gives the main values: rated operational voltage up to 690 V (50 Hz), rated impulse withstand voltage 12 kV (depending on design type), rated insulation voltage 1,000 V, pollution degree 3, horizontal main busbar rated current up to 7,010 A, rated peak withstand current up to 330 kA and rated short-time withstand current up to 150 kA for 1 s. Device currents are up to 6,300 A for circuit-breakers and up to 630 A for cable and motor feeders. Internal separation is form 1 to form 4 per IEC 61439-2 and up to form 4b type 7 per BS EN 61439-2; degree of protection is IP43 ventilated, IP54 non-ventilated, with mechanical strength up to IK10.
Cubicles are 2,000 or 2,200 mm high, with nine widths between 200 and 1,400 mm (200, 350, 400, 600, 800, 850, 1,000, 1,200, 1,400) and depths of 500, 600, 800 mm (single front) and 1,000, 1,200 mm (double front). The manual treats six mounting designs in separate chapters: circuit-breaker design (3WA), universal mounting, in-line plug-in, fixed-mounted, frequency converter design and reactive power compensation. The communication chapter covers serial fieldbus, Ethernet-based systems and gateways.
In the planning notes, weights (circuit-breaker cubicles about 340-390 kg for 630-1,600 A, 510-545 kg for 2,000-3,200 A, 770 kg for 4,000 A and 915 kg for 4,000-6,300 A) and power losses (for example 3WA1106, 630 A: 215 W at rated current and 140 W at 80%; 3WA1116, 1,600 A: 1,000 W and 640 W) are given as approximate values. The arc resistance chapter covers the IEC/TR 61641 test, passive and active arc protection and the advice to consider a 300 ms arc duration for assemblies fed by a transformer. Annexes cover network systems, load dimensioning, degrees of protection, forms of internal separation, motor currents and transformers. The document is specific to Siemens products; numerical values depend on the chosen configuration.
Key points
- Horizontal main busbar rated current up to 7,010 A; rated peak withstand current Ipk up to 330 kA; rated short-time withstand current Icw up to 150 kA for 1 s.
- Rated operational voltage up to 690 V (50 Hz); rated insulation voltage 1,000 V; rated impulse withstand voltage 12 kV; pollution degree 3.
- Device currents: circuit-breaker up to 6,300 A; cable feeders and motor feeders up to 630 A.
- Internal separation form 1-4 per IEC 61439-2, up to form 4b type 7 per BS EN 61439-2; IP43 ventilated, IP54 non-ventilated; mechanical strength up to IK10.
- Dimensions: height 2,000/2,200 mm; widths 200, 350, 400, 600, 800, 850, 1,000, 1,200, 1,400 mm; depths 500, 600, 800 mm (single front), 1,000, 1,200 mm (double front).
- Six mounting designs: circuit-breaker (3WA), universal mounting, in-line plug-in, fixed-mounted, frequency converter and reactive power compensation.
- Indicative weights: breaker cubicle 340-390 kg for 630-1,600 A, 510-545 kg for 2,000-3,200 A, 770 kg for 4,000 A and 915 kg for 4,000-6,300 A.
- Power losses (rated / 80% current): 3WA1106 (630 A) 215 / 140 W; 3WA1110 (1,000 A) 540 / 345 W; 3WA1116 (1,600 A) 1,000 / 640 W.
- For arc faults: IEC/TR 61641 test, passive protection (insulated busbars, barriers), active arc detection and a 300 ms arc duration advice for transformer-fed assemblies.
Using it in design
- In switchboard selection, compare the 7,010 A busbar and 6,300 A breaker limits and the Icw 150 kA / Ipk 330 kA values with the fault-current study.
- Place cubicle dimensions (width 200-1,400 mm, depth 500-1,200 mm) in the electrical room plan and add the indicative weights to floor loading.
- Add power losses (for example 1,000 W for a 1,600 A 3WA at 100% current) to the electrical room cooling load; lower values at 80% load can be used.
- For a data centre, state the form of internal separation (such as form 3b or 4b) in the specification and choose IP43/IP54 to suit room conditions.
- For arc fault risk, add the IEC/TR 61641 test certificate, arc barriers and if needed active arc detection to the specification; allow for the 300 ms arc duration on transformer-fed assemblies.
Who should read it
Electrical engineers who design, specify and size low-voltage switchboard systems.
Document contents
- 1 System-based power distribution
- 2 SIVACON S8 system overview
- 3 Circuit-breaker design
- 4 Universal mounting design
- 5 In-line design, plug-in
- 6 Fixed-mounted design
- 7 Reactive power compensation
- 8 Communication connection
- 9 Further planning notes: installation, weights and power losses, environmental conditions
- 10 Conformance to standards and design verification: IEC 61439-2, arc resistance, seismic withstand capability, declarations of conformity
- 11 Technical annex
- 12 Glossary and rated values
Publication details
- Authors
- Siemens
- Publisher
- Siemens
- Year
- 2025
- Document number
- SIVACON S8, status 01/2025 V3-korr
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Publisher source opened. No document-specific commercial redistribution permission established; link and original metadata only.
Citation
Siemens (2025). SIVACON S8: Technical Planning Information. Siemens. SIVACON S8, status 01/2025 V3-korr. https://cache.industry.siemens.com/dl/files/936/107113936/att_1342112/v1/TIP_Planning_manual_SIVACON_S8_2025-02_EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.