Sinorix Silent Extinguishing Technology - protecting the quiet way
Siemens Smart Infrastructure · Siemens Switzerland Ltd
A 2013 Siemens brochure explaining that gas discharge noise can disable hard disk drives (HDDs), and presenting a silent nozzle, Sinorix Compact (up to 120 m3) and the constant-flow Sinorix CDT.
On this page
Overview
The brochure states that the high noise from a triggered dry extinguishing system can cause hard disk drive malfunctions. Studies by Siemens and independent organisations identify the discharge noise level as the main cause. Improving room acoustics or extending discharge time can reduce noise, but Siemens research points to nozzle design as the main contributor.
At the centre is the Sinorix Silent Nozzle, with a linear design that directs the gas discharge, and hence the sound, in a predefined direction and keeps noise below the level that puts HDDs at risk. The nozzle pairs with two systems: Sinorix Compact for small server rooms up to 120 m3, integrating detection, extinguishing, alarm and control in one cabinet (Novec 1230 agent), and Sinorix CDT for medium to large data centres using nitrogen or argon.
The distinguishing feature of Sinorix CDT is a pressure-regulating cylinder valve. The agent is released at constant mass flow over the whole flooding time, which removes the peak at the start of discharge and lowers noise. The system can be sized as single- or multi-sector, cylinders can be central or decentralised, and overpressure flaps can be reduced by up to 70 percent.
The document is a product brochure: agent properties and benefits are manufacturer claims, and no numerical noise threshold is given. Its value for design is that it frames discharge noise as a risk to storage equipment that belongs in extinguishing selection.
Key points
- Noise from dry extinguishing discharge can cause HDD malfunctions; the brochure names it as the main cause.
- The Sinorix Silent Nozzle's linear design directs the gas discharge and its sound in a set direction.
- Sinorix Compact combines detection, extinguishing, alarm and control in one cabinet for server rooms up to 120 m3.
- Sinorix Compact uses 3M Novec 1230: non-conductive, non-corrosive, ozone depletion potential 0, atmospheric lifetime 3 to 5 days, global warming potential 1.
- Sinorix CDT uses nitrogen or argon and a pressure-regulating cylinder valve for constant mass flow during flooding.
- Constant flow removes the initial discharge pressure peak; overpressure flaps can be up to 70 percent smaller.
- Sinorix CDT can be single- or multi-sector, with a central or decentralised cylinder battery.
Using it in design
- For HDD-heavy halls, write discharge noise into the gas suppression specification as its own criterion and ask the vendor for test data on limited discharge noise.
- Evaluate nozzle type, discharge time and room acoustics together; removing the initial peak with constant-flow systems affects both noise and relief flap area.
- Where relief area is restricted, check how a low-peak system changes flap size.
- Compare agents (Novec 1230, nitrogen, argon) against room volume, cylinder space and personnel safety needs.
Who should read it
Engineers designing data centre and server room fire suppression and operators assessing risk to storage equipment.
Document contents
- Data centers and server rooms: challenges for extinguishing
- Quiet extinguishing is the key
- Unique nozzle design
- Protecting small to large applications
- All-in-one safety with Sinorix Compact
- Constant mass flow with Sinorix CDT
- Clean extinguishing agents
Related standards
- ISO 14520
- EN 15004
- NFPA 2001
Publication details
- Authors
- Siemens Switzerland Ltd
- Publisher
- Siemens Smart Infrastructure
- Year
- 2013
- Document number
- BT_0045_EN
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
© Siemens Switzerland Ltd, 2013 (p. 6)
Citation
Siemens Switzerland Ltd (2013). Sinorix Silent Extinguishing Technology - protecting the quiet way. Siemens Smart Infrastructure. BT_0045_EN. https://assets.new.siemens.com/siemens/assets/api/uuid:88d70da0-d652-43c9-97fd-f58221e26688/sinorixsilentextinguishingtechnology.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.