Stefani Eagle Fan Dry Coolers Catalogue (SDS, SDL, SDNV)
Original title Eagle Fan Dry Coolers catalogue
Stefani
Stefani's Eagle Fan dry cooler catalogue: SDNS, SDNL, SDS, SDL and SDNV series, capacities per EN 1048 at 34% ethylene glycol, 25°C air and 40/35°C fluid; coils are tested at 33 bar dry air.
On this page
Overview
The catalogue presents Stefani's Eagle Fan dry cooler family, covering SDNS/SDNL (035, 050, 063 mm fans), SDS/SDL (080-090 mm), SDNV (6 and 8-12 poles) and DUAL models, in Italian, English, German and French. Each series has performance and dimension pages and an installation advice section. Each fan type has two heat exchanger lengths: short S, very compact for limited space, and long L, with low fan power and low noise. DUAL models have two independent fluid circuits and two independent rows of fans.
Declared capacities comply with EN 1048 and rest on one condition: 34% ethylene glycol, air at 25°C, fluid in at 40°C and out at 35°C. Performance tables give per-model capacity (kW), airflow (m³/h), fluid flow, fluid pressure drop (bar), sound pressure level at 10 m in dB(A), fan count and diameter, surface area, connection sizes, tube volume and weight. For example SDNS 035/1 A is 7.2 kW, 2,700 m³/h, 40 dB(A) and 18 kg; the large SDNV 080/8.2 rows run to several hundred kW.
Construction: RAL 9002 epoxy-painted galvanised steel casing, galvanised coil frame, copper tubes and aluminium fins, headers and bends guarded by panels from 500 mm fan diameter, high-efficiency IP54 fan motors with thermal protection and separate fan sections. Coils are tested at 33 bar with dry air. Options: pre-coated aluminium or copper fins, stainless steel tubes and casing, cataphoresis, single-phase or explosion-proof fans, and a speed controller with temperature sensor. Guarantee is 2 years.
Key points
- Capacity condition: EN 1048, 34% ethylene glycol, air 25°C, fluid in 40°C, out 35°C.
- Series: SDNS, SDNL (fans 035, 050, 063), SDS, SDL (080-090), SDNV (6 and 8-12 poles) and DUAL versions.
- Heat exchanger in two lengths, S (short, compact) and L (long, low fan power and noise), plus a V option.
- Example model SDNS 035/1 A: 7.2 kW, 2,700 m³/h, 0.46 bar fluid pressure drop, 40 dB(A), 18 kg.
- Casing RAL 9002 epoxy-painted galvanised steel; coil copper tube and aluminium fin; fan motors IP54 with thermal protection.
- Coil test pressure 33 bar dry air; guarantee 2 years.
- Options: stainless steel tubes and casing, cataphoresis, coated or copper fins, explosion-proof fans and speed controller.
- Ordering code: series, coil module (S, L, SL, LL, V), fan diameter, fan count, coil (A, B, C), fan poles, motor connection, air direction (vertical V or horizontal H).
Using it in design
- Do not use capacities without correcting from 25°C air and 40/35°C fluid to your own design air temperature (35-40°C in data centres) and fluid temperatures.
- Choose between S and L modules on the footprint versus fan power and noise balance; short for dense layouts, long for noise-sensitive sites.
- Evaluate the A, B, C coil options together with fluid pressure drop and air-side performance.
- Apply the installation advice clearance rules (distances between units and to a wall in multiples of W and W/2) in the layout.
- In cold climates, select glycol share and the fan speed controller to define the operating range.
Who should read it
Mechanical designers selecting dry coolers and procurement engineers comparing products.
Document contents
- Description
- Performance tables (SDNS, SDNL, SDS, SDL, SDNV, DUAL)
- Dimensions
- Advice for installation
- Ordering code
- Guarantee
Publication details
- Authors
- Stefani
- Publisher
- Stefani
- Year
- Year not stated
- Document language
- Multilingual
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document