Technical guideFree to read2021

STULZ Explorer WSW: Water-Cooled Chillers for Critical Applications (French brochure, 2021)

Original title Explorer WSW brochure

Stulz

STULZ's 2021 brochure: the Explorer WSW water-cooled screw chiller series on R513A, 230-1,529 kW, ESEER 6.5-7.1, with a CyberCool Free Cooling Booster example saving 127,867 € a year.

On this page

Overview

The brochure presents the Explorer WSW series, designed for industrial, IT and comfort air conditioning and completing STULZ's high-efficiency chiller family. Common features of all modules are R513A refrigerant (no ozone depletion, lower GWP than traditional refrigerants), indoor installation (control cabinet IP 54), ErP 2021 Ecodesign compliance and a silent version in which compressors are the only noise source; silent versions are up to 10 dB lower depending on operating condition.

For data centre and telecom applications, chilled water at the evaporator is +12 to +22 °C in and +7 to +18 °C out; process cooling 0-30 °C in and +5 to +25 °C out; comfort air conditioning +12 to +20 °C in and +7 to +15 °C out. Options extend the operating range to very low and very high temperatures, so the chiller can work with dry coolers (high temperature), cooling towers (medium) or well water (low).

Models have one or two screw compressors. Single-circuit WSW 080-140 give 230-429 kW cooling, EER 5.06-5.15 and ESEER (ISO 14511) 6.87-7.11; larger two-circuit models run from 459 kW to 1,529 kW with ESEER of 6.55-7.03. The brochure explains EER, ESEER (weights of 3, 33, 41 and 23 percent at 100/75/50/25 percent load) and STULZ's VICP coefficient (weights of 1, 42, 45 and 12 percent).

The CyberCool Free Cooling Booster takes the compressor out when outdoor air is cool. In an example for the Hamburg temperature curve, 18/12 °C water, a WSW360 chiller, WFM04 module and two EHLD1F 1267E dry coolers at 0.15 €/kWh, the system uses 1,380,025 kWh with free cooling and 2,232,472 kWh without; cost is 207,004 € versus 334,871 €, a saving of 127,867 € a year. Operating hours are about 2,478 in compressor mode, 3,199 in mixed mode and 3,083 in free cooling mode.

Key points

  1. Cooling capacity ranges from 230 kW (WSW 080) to 1,529 kW; refrigerant is R513A.
  2. In data centre use, evaporator inlet/outlet water is +12 to +22 °C / +7 to +18 °C.
  3. Single-circuit WSW 080-140: EER 5.06-5.15, ESEER (ISO 14511) 6.87-7.11.
  4. The larger two-circuit models have ESEER values of 6.55-7.03.
  5. ESEER weights are 0.03 at 100 percent load, 0.33 at 75, 0.41 at 50 and 0.23 at 25.
  6. The silent version lowers sound by up to 10 dB depending on operating condition; control cabinet is IP 54.
  7. Example (Hamburg, 18/12 °C, 0.15 €/kWh): 1,380,025 kWh with free cooling, 2,232,472 kWh without; annual saving 127,867 €.
  8. In the free cooling example, about 2,478 h compressor, 3,199 h mixed and 3,083 h free cooling mode.

Using it in design

  • Compare the hall chilled water regime (for example 18/12 °C) with the model's +12/+22 °C in and +7/+18 °C out range.
  • For high water temperature designs, simulate the free cooling module's annual hour distribution against the local temperature curve.
  • Plan the condenser side (dry cooler, cooling tower or well water) consistent with the options.
  • Select on part-load ESEER and redundancy steps, not only full-load EER.
  • Recalculate the brochure's energy saving example with your own site climate and electricity price; values are for Hamburg and 0.15 €/kWh.

Who should read it

Mechanical engineers designing data centre chilled water plants and writing chiller specifications.

Document contents

  1. About STULZ
  2. Smart solution for critical applications (R513A, ErP 2021, indoor, silent operation)
  3. Water temperatures by application
  4. Reliability
  5. EER, ESEER and VICP
  6. CyberCool Free Cooling Booster
  7. Installation
  8. Technical data and performance data

Publication details

Authors
Stulz
Publisher
Stulz
Year
2021
Document language
French
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Stulz (2021). Explorer WSW brochure. Stulz. https://www.stulz.com/fileadmin/user_upload/products/Brochures_Manuals/Explorer/STULZ_Explorer_WSW_Brochure_2107_FR.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.