Tecnair P series precision cooling
Original title Tecnair Close Control Air Conditioners 2023, Packaged P-series technical table
Tecnair
The Tecnair 2023 brochure lists DX and chilled-water close control series; in the packaged P-series, DX models give 8.2-94.9 kW and chilled-water models 9.9-160 kW cooling, and capacities exclude fan heat.
On this page
Overview
Tecnair's 2023 close control brochure presents DX air conditioners with air-cooled or water-cooled condensers and chilled-water units for data centres and special applications. In the packaged P-series, UPA/OPA DX models run from 71 to 932 in 14 models with 8.2-94.9 kW cooling, 2,200-21,000 m³/h airflow and 51-67 dB(A) sound pressure. UPU/OPU chilled-water models, 10 to 220 in 10 models, reach 9.9-160 kW.
For large data centres there are the UGA and UGU series. UGA DX models 932 and 1342 give 102.6 and 153.9 kW, while UGU chilled-water models 70 to 300 give 55.5-220.7 kW. In these series the fans sit in the large space under the raised floor so the footprint does not grow. The Cold Wall (HWU) series is a chilled-water unit installed in service corridors, giving 112-500.5 kW from 2X1 to 4X2.
On controls, the Survey3 microprocessor offers a 320 x 240 pixel colour display and Modbus RTU, Modbus IP, optional BACnet IP and BACnet MS/TP. The SMART NET local network shares workload across units and claims up to 60% energy savings over redundant N+1 or N+N networks. POWER VALVE balances water flow independent of pressure and monitors EER.
Table capacities exclude fan heat, which must be added to the system heat load. Values are tied to specific intake conditions: 24 °C and 45% RH for the P-series, 32 °C and 30% RH for UGA/UGU, and 40 °C and 25% RH for Cold Wall. Table capacity therefore cannot be used directly as net sensible capacity.
Key points
- P-series DX (UPA/OPA): 14 models, 8.2-94.9 kW, EER 3.13-3.83, 2,200-21,000 m³/h, 51-67 dB(A).
- P-series chilled water (UPU/OPU): 10 models, 9.9-160 kW; 24 °C and 45% RH, 7/12 °C water.
- UGA DX: models 932 and 1342 at 102.6 and 153.9 kW; UGU chilled water 55.5-220.7 kW.
- Cold Wall (HWU): 2X1-4X2 combinations, 112-500.5 kW; 40 °C and 25% RH, 20/30 °C water.
- Capacity excludes fan heat; add fan heat to the load.
- SMART NET: load sharing across the local network, up to 60% energy savings versus N+1 or N+N networks claimed.
- Survey3 control: Modbus RTU/IP, optional BACnet IP and MS/TP; e-mail alert accessory.
- SMART COOL: electronic expansion valve, active superheat and subcooling control, over 15 control and over 20 safety functions.
Using it in design
- Add fan heat to the heat load to convert table capacity to net sensible capacity, and correct for the difference between table conditions and project return air.
- Check raised floor height (550-1,000 mm) and the effect on footprint of the UGA/UGU design that places fans below the floor.
- In load-sharing local networks such as SMART NET, assess the redundancy scheme (N+1) and part-load efficiency separately.
- If the BMS needs BACnet, state in the specification that it is an accessory.
- For the service-corridor Cold Wall option, match corridor width and water connection side with the building design.
Who should read it
Mechanical designers selecting DX or chilled-water close control units for data halls.
Document contents
- Electronic control system
- Advanced cooling circuit
- SMART NET local network
- UPA/OPA DX air conditioners
- UPU/OPU chilled-water air conditioners
- UGA and UGU large data-centre units
- Cold Wall service-corridor units
Publication details
- Authors
- Tecnair
- Publisher
- Tecnair
- Year
- 2023
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Tecnair (2023). Tecnair Close Control Air Conditioners 2023, Packaged P-series technical table. Tecnair. https://thermocontrol.no/wp-content/uploads/2022/06/Brosjyre-Tecnair_2023_EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
