Teknopomp TNL In-Line Dry-Rotor Circulation Pumps: Installation, Operation, Maintenance and Repair Manual
Original title TNL In-Line Tip Kuru Rotorlu Sirkülasyon Pompaları: Montaj, İşletme, Bakım ve Onarım Kılavuzu
Teknopomp
Teknopomp's TNL in-line circulation pump manual gives installation, commissioning and maintenance steps for liquids up to 90 °C and a 10 bar outlet pressure limit, and prohibits dry running.
On this page
Overview
The 28-page Turkish manual contains instructions for installing, commissioning and maintaining Teknopomp's TNL-type, non-self-priming, single-stage volute in-line centrifugal pumps. The pumps conform to DIN 24255 within their nominal capacity range. Applications listed include water networks and pressure boosting, irrigation and drainage, hot or cold water circulation in heating and cooling systems, condensate pumping, swimming pools and industrial plants.
The suitable medium is thin, clean, non-abrasive liquid without coarse solid particles or fibres, with a temperature up to 90 °C. Pressure at the outlet flange must not exceed 10 bar while running. The manual covers personnel training, the dangers of ignoring safety instructions, electrical safety (EN 60204-1), transport and storage (draining against freezing, antifreeze), site, coupling adjustment and piping rules.
In piping, the pump must not be used as a pipe support, the suction pipe should rise toward the pump and air accumulation in the pump must be avoided. The motor connection is three phase; pump motors that need high starting torque must not be star-delta connected. If star-delta is used, the timer is set to a maximum of 30 seconds. For frequency-controlled motors, high starting torque and suitable cooling at low speed must be provided. The motor is protected with a thermal or thermal-magnetic relay.
Before commissioning the pump and suction pipe are filled with water and vented; dry running is prohibited. Rotation is clockwise looking from the motor toward the pump. For operation that may reach zero flow, a minimum-flow valve is needed to limit overheating. The maintenance section covers mechanical seal checks (water leaking from the seal shows wear), running the standby pump briefly once a week, the lifetime-greased motor bearing, dismantling and assembly steps, and recommended spare part quantities.
Key points
- TNL: single-stage, volute, in-line, non-self-priming centrifugal pump; conforms to DIN 24255.
- Medium temperature up to 90 °C; outlet flange pressure must not exceed 10 bar while running.
- The pump and suction pipe are filled with water before starting; dry running is prohibited.
- A minimum-flow valve limits overheating where operation may reach zero flow.
- If star-delta is used, the timer is at most 30 seconds; pumps needing high starting torque are not star-delta connected.
- The motor is protected by a thermal or thermal-magnetic relay against overload and short circuit.
- Mechanical seal: leakage indicates wear; the standby pump is run briefly once a week.
- In storage the water is drained and antifreeze and rust inhibitor are applied.
Using it in design
- Check the pump outlet pressure (static head included) in the cooling-water circuit against the 10 bar limit; choose another series for liquids above 90 °C.
- Provide a rising suction slope and air-vent points in the piping; design supports separately so that pipe loads do not reach the pump flanges.
- In circuits that may run at low load or close off, include a minimum-flow line and valve in the design.
- In duty/standby arrangements, write pump rotation and the weekly test run into the operating procedure.
- Set the motor protection relay to nominal current; if a frequency converter is used, verify motor cooling.
Who should read it
Mechanical engineers and technicians who design pump rooms and carry out installation and commissioning.
Document contents
- Introduction
- General (pump description, applications, technical specifications, pressure limit)
- Safe operating conditions
- Transport and storage
- Installation (site, coupling, piping, motor connection)
- Commissioning and stopping
- Maintenance (parts check, bearings, mechanical seal, service, spare parts)
- Disassembly and assembly
Publication details
- Authors
- Teknopomp
- Publisher
- Teknopomp
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer documentation inspected. No redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.
Citation
Teknopomp TNL In-Line Tip Kuru Rotorlu Sirkülasyon Pompaları: Montaj, İşletme, Bakım ve Onarım Kılavuzu. Teknopomp. https://www.teknopomp.com/wp-content/uploads/2023/02/TNL-Kullanim-Kilavuz-Low.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.