Technical guideFree to read2025

Teksan Data Center Power Solutions

Teksan

This two-page 2025 Teksan brochure summarises generator power classes for data centres, resilience options and synchronisation schemes; its most useful part is the power-class rating table.

On this page

Overview

The core of the brochure is a table contrasting Standby, Prime, Continuous and ISO 8528-1:2018 DCP on load profile, annual hours and average load. Standby is defined at 200 hours per year and 70% average load, Prime at unlimited hours and 70%, and Continuous at unlimited hours and 100% fixed load. DCP allows unlimited hours, but because ISO leaves the average load undefined, it is to be treated as a maximum of 100%.

The critical limit of DCP is that it excludes prolonged parallel operation with the utility. A DCP-rated basis is therefore unsuitable if the gensets will also serve peak shaving or utility-parallel duty. The class definition sets no load-factor limit and covers unlimited hours at constant or variable load.

The brochure then lists options. On controls: redundant or hot-standby control system, double AVR and PMG excitation. On the mechanical side: redundant electric starter and battery group, double-bearing and class F alternators. For fuel: double-skinned underground or above-ground main tanks, leak detection, automatic filling with redundant pumps and fuel polishing. The synchronisation schemes are multiple-set standby to mains with break or no-break return, multiple mains supplies, and a single set serving multiple mains. The material is marketing-level and contains no calculation method.

Key points

  1. DCP (ISO 8528-1:2018) is continuous power for unlimited hours at constant or variable load, with no load-factor limit.
  2. Prolonged parallel operation with the utility is not allowed under DCP.
  3. Standby: 200 h/yr at 70% average load.
  4. Prime: unlimited hours at 70% average load; Continuous: unlimited hours at 100% fixed load.
  5. DCP average load is undefined in ISO and should be treated as a maximum of 100%.
  6. Resilience options: redundant control, double AVR, PMG, redundant electric starter and battery group, double-bearing and class F alternator.
  7. Synchronisation: multiple-set standby to mains with break or no-break return, multiple mains, single set to multiple mains.
  8. Fuel options: double-skinned tanks, leak detection, automatic filling with redundant pumps, fuel polishing.

Using it in design

  • Record the DCP generator rating and verify the source’s restriction on utility-parallel operation.
  • If the design uses gensets for peak shaving or utility-parallel operation, add a rule that blocks a DCP-rated basis.
  • For Tier III/IV, put redundant controls/AVR/starters, redundant fuel transfer pumps, leak detection and polishing on the option checklist.
  • Include seismic isolators in the selection where the site seismic zone requires them.

Who should read it

Electrical designers choosing a generator rating class from manufacturer catalogues, and catalogue or rule developers encoding those classes.

Related standards

  • ISO 8528-1:2018
  • Uptime Institute Tier Standard: Topology

Publication details

Authors
Teksan
Publisher
Teksan
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Teksan (2025). Teksan Data Center Power Solutions. Teksan. https://cdn.teksan.com/files/data-center-power-solutions.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.