White paperFree to read2020

Data Center White Paper: The Importance of Generators in Data Centers

Teksan

This short 2020 Teksan white paper argues that data-centre generator reliability depends on the whole set and its full life cycle, from installation to spare parts, and not only on fast start capability.

On this page

Overview

The paper treats the generator as a holistic system rather than a single machine. It lists the set and all its auxiliaries, site conditions, installation, commissioning, maintenance and spare-parts supply as the factors that decide reliability. Fast start is not accepted as a sufficient criterion on its own; the weakest link in the chain determines the outcome even when the engine itself performs well.

The technical framing rests on three points. First, the generator must start and pick up load before the UPS stored energy runs out, because UPS autonomy is limited. Second, whatever the rating class (DCP, Prime or Standby), the complete set of engine, alternator, radiator, controls and starting system is expected to conform to ISO 8528. Third, block water heaters are fitted as standard, while a backup starter, a backup electric starter and backup battery systems are options.

For plant-room design the paper names ventilation back pressure, room temperature rise and its effect on equipment, and exhaust back pressure, and recommends verifying them with 3D flow simulation. Tier IV allowable downtime is cited as about 0.8 hours per year. The text is largely qualitative with limited numeric content; it reflects a manufacturer's viewpoint and gives no calculation method or acceptance values.

Key points

  1. Tier IV allowable downtime is cited as about 0.8 h per year.
  2. The generator must start and take load before UPS stored energy is exhausted; UPS autonomy is limited.
  3. Regardless of DCP, Prime or Standby rating, the complete set of engine, alternator, radiator, controls and starting system should conform to ISO 8528.
  4. Reliability is not limited to fast start; the set, auxiliaries, site, installation, commissioning, maintenance and spare parts are assessed together.
  5. Block water heaters are standard; backup starter, backup electric starter and backup battery systems are offered as options.
  6. Plant-room ventilation back pressure, room temperature rise and exhaust back pressure are verified with 3D flow simulation.
  7. Mechanical and vibration verification is treated as part of the holistic approach.

Using it in design

  • Compare the generator start-plus-transfer time with UPS autonomy and show the margin in the design file.
  • Calculate room ventilation airflow against the radiator requirement, the room temperature rise and the external static/back-pressure limits.
  • Check exhaust back pressure against the limit on the manufacturer datasheet.
  • For Tier III/IV targets, treat the block heater as default and add options such as redundant starters and batteries to the checklist.

Who should read it

Electrical designers preparing generator rooms and standby power schemes, and the operations and commissioning teams behind them.

Related standards

  • ISO 8528-1
  • ISO 8528-5

Publication details

Authors
Teksan
Publisher
Teksan
Year
2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Teksan (2020). Data Center White Paper: The Importance of Generators in Data Centers. Teksan. https://cdn.teksan.com/files/data-center-white-paper.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.