Diesel Generator Sets: Maintenance and Operation Manual
Original title Dizel Jeneratör Setleri: Bakım ve Kullanım Kitabı
Teksan
Teksan's 2023 Turkish maintenance and operation manual covering installation (150-200 mm concrete base, ventilation window at least the radiator area), control systems and maintenance; it advises at least 30% load for ESP and PRP sets.
On this page
Overview
The manual covers safety precautions, general definitions, installation, control systems, maintenance, a troubleshooting guide and warranty in seven chapters. Safety lists lifting and handling (lifting gear must withstand at least 10% more than gross weight), moving and hot parts, fire and explosion, toxic materials, environmental protection and electrical risks. General definitions introduce canopy, container, slide-in canopy and trailer set types, and the engine, alternator, fuel tank, chassis, vibration isolators, exhaust and controls.
The installation chapter is the most useful for data-centre and facility designers. The base must not exceed the floor load limit; reinforced concrete, typically 150-200 mm thick and at least the set's footprint, raised at least 300 mm where flooding is a risk. Ventilation windows open behind the alternator for cold air in and in front of the radiator for hot air out, at least the radiator core area and preferably 150% of it; automatic standby sets need automatic louvres. For exhaust the main aim is no back pressure; bend radius 150% of pipe inner radius, pipes at least 250 mm from combustibles and a separate exhaust for each machine. Fuel system, noise control, fire precautions and earthing are also covered.
The operation and maintenance chapters stress low-load operation: the minimum permitted load is 30% of full power for ESP and PRP category sets and 25% for COP. The unloaded weekly test should be limited to 10 minutes, oil and fuel filters of lightly loaded sets replaced every six months, and a 4-hour run at 75% load once a year is advised. Low load causes unburnt fuel, carbon build-up, turbo oil leaks and white smoke. For storage beyond three months a special procedure applies.
Key points
- Base: reinforced concrete, 150-200 mm thick, at least the set footprint; at least 300 mm above floor where flooding is possible.
- Ventilation window at least the radiator core area, preferably 150%; automatic louvres needed on automatic standby sets.
- Exhaust: no back pressure as the main aim; bend radius 150% of pipe inner radius, pipes 250 mm from combustibles, a separate exhaust per machine.
- Lifting gear must withstand at least 10% more than the gross weight of the set.
- Fuel tank: at least 300 mm between inlet and outlet; black steel, suitable plastic or copper pipe.
- Minimum load is 30% of full power for ESP and PRP sets and 25% for COP; the unloaded weekly test is limited to 10 minutes.
- A 4-hour run at 75% load each year and six-monthly filter changes for lightly loaded sets are advised; a load bank is used if load is lacking.
- Storage under three months: keep in a dry place in protective packing and run briefly at least every 15 days; a special procedure applies above three months.
Using it in design
- In generator room and base design, check the 150-200 mm concrete base, 300 mm raising (flooding risk) and vibration isolation requirements.
- Size air inlet and discharge windows not smaller than the radiator core area (target 150%) and provide automatic louvres for automatic standby sets.
- In exhaust design, verify a separate line per set, a short route, the bend radius rule, 250 mm clearance from combustibles and the discharge point.
- Plan testing with a load bank or real load rather than unloaded runs; the weekly unloaded test should not exceed 10 minutes.
- Include the shortened filter change interval for low-load operation and the annual 4-hour high-load run in the maintenance contract.
Who should read it
Technical staff who install, operate and maintain generators, and engineers designing generator rooms and bases.
Document contents
- Safety precautions
- General definitions
- Installation
- Control systems
- Maintenance
- Troubleshooting
- Warranty
Publication details
- Authors
- Teksan
- Publisher
- Teksan
- Year
- 2023
- Document number
- BBK-V.0123_TR
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Üreticinin herkese açık kaynağı okundu. Açık erişim yeniden dağıtım izni değildir; tam metin kütüphaneye alınmaz. Ana bölüm altlıkları BBK-V.0123_TR; giriş s. 3 eski BBK-V.122018_TR kodunu korur. 2023 yılı ana bölüm revizyon koduna dayanır; belge tekdüze revizyon bilgisi taşımıyor.
Citation
Teksan (2023). Dizel Jeneratör Setleri: Bakım ve Kullanım Kitabı. Teksan. BBK-V.0123_TR. https://www.teksan.com/files/Dizel-Jenerator-Kullanim-Kilavuzu.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.