Technical guideFree to read2023

Emergency backup diesel engines on installations: best available techniques (BAT)

Environment Agency, United Kingdom

A UK Environment Agency guidance of 21 August 2023 for emergency backup diesels classed as new medium combustion plant running up to 500 hours a year: a guidance level of about 750 mg/m3 NOx (15% O2) and under 50 hours of testing a year.

On this page

Overview

The guidance applies in England to emergency backup diesel engines on Industrial Emissions Directive (IED) installations that run up to 500 hours a year and are classed as new medium combustion plant exempt from emission limit values (ELVs). It covers Part A 1.1 combustion installations above 50 MWth and activities directly associated with IED installations; static and mobile engines are included, temporary mobile plant is not. Example uses include black start, emergency backup at data centres, manufacturing sites, the electricity balancing market (when NOx is abated) and large construction sites.

The text states that unabated diesel engines emit high levels of NOx and can breach short-term air quality standards within a few hours of operation, especially where significant capacity is installed. As a minimum, Schedule 25A of the medium combustion plant directive and Schedule 25B of the specified generators regulation must be met. As a build standard, engines must be emissions optimised; fuel-optimised engines do not meet BAT without secondary abatement. Specification sheets meeting the former 2g TA Luft or US EPA Tier 2 (or equivalent) standards are accepted as proof of BAT and need no on-site exhaust monitoring.

The guidance level is about 750 mg/m3 NOx (as NO2, 15% O2, dry, 273 K and 101.3 kPa), equivalent to 2,000 mg/m3 at 5% O2 (commonly '2g'), at a typical emergency load (usually above 67% of standby rating). Stacks must be vertical and unobstructed by caps or cowls. Operational controls: test for under 50 hours a year, avoid testing when air quality is poor and do not test more than one engine at a time.

Key points

  1. Scope: emergency backup diesels classed as new medium combustion plant exempt from ELVs, up to 500 hours a year (IED installations, Part A 1.1 combustion above 50 MWth).
  2. Uses: black start, data-centre emergency backup, manufacturing sites, balancing market (when NOx is abated), large construction sites.
  3. Unabated diesels emit high NOx and can breach short-term air quality standards within a few hours.
  4. Engines must be emissions optimised; fuel-optimised engines do not meet BAT without secondary abatement.
  5. Guidance level: about 750 mg/m3 NOx (15% O2), equivalent to 2,000 mg/m3 (5% O2, '2g'), at loads above 67% of standby rating.
  6. 2g TA Luft or EPA Tier 2 (or equivalent) specification sheets are proof of BAT; no on-site exhaust monitoring is needed.
  7. Stacks must be vertical, with emissions unobstructed by caps or cowls.
  8. Testing must be under 50 hours a year, not in poor air quality and one engine at a time.

Using it in design

  • In generator tenders and specifications, require 2g TA Luft or EPA Tier 2 compliance and the 750 mg/m3 NOx (15% O2) guidance level on the engine data sheet.
  • Design the exhaust stack vertical and uncapped; evaluate discharge direction and height for dispersion.
  • Plan the test programme at under 50 hours a year and schedule tests around air quality conditions and the one-engine rule.
  • For multi-generator data-centre campuses, assess the short-term air quality effect of total installed capacity in the permit application.
  • Attach engine specification sheets to the permit application.

Who should read it

Engineers and environmental permitting specialists designing diesel-backed data centres and facilities in England or under similar permit regimes.

Document contents

  1. Scope
  2. Examples of use
  3. Regulatory requirements
  4. Build standards
  5. Operational controls
  6. Contact the Environment Agency

Publication details

Authors
Environment Agency, United Kingdom
Publisher
Environment Agency, United Kingdom
Year
2023
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Opened GOV.UK guidance explicitly applies to England; page footer grants Open Government Licence v3.0 except otherwise stated. Published 21 August 2023. Round 5/6 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Environment Agency, United Kingdom (2023). Emergency backup diesel engines on installations: best available techniques (BAT). Environment Agency, United Kingdom. https://www.gov.uk/guidance/emergency-backup-diesel-engines-on-installations-best-available-techniques-bat

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.