Large Energy Users Connection Policy - Decision Paper (CRU/2025236)
Commission for Regulation of Utilities (Ireland) · Commission for Regulation of Utilities (CRU)
Ireland's final decision (12 December 2025) on how new data centres may connect to the electricity grid, replacing the 2021 direction.
On this page
Overview
Connections are tiered by Maximum Import Capacity: under 1 MVA exempt, 1-10 MVA must self-supply as behind-the-meter autoproducers, and 10 MVA or more must bring dispatchable onsite or proximate generation and/or storage matching their MIC. All in-scope sites must also source at least 80% of annual demand from additional Irish renewable generation. Essential for anyone siting or sizing a data centre in Ireland.
Related standards
- EU Directive 2023/1791 (EED) Article 12
Publication details
- Authors
- Commission for Regulation of Utilities (CRU)
- Publisher
- Commission for Regulation of Utilities (Ireland)
- Year
- 2025
- Document number
- CRU/2025236
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Irish regulator decision paper; no open licence statement found in the document.
Citation
Commission for Regulation of Utilities (CRU) (2025). Large Energy Users Connection Policy - Decision Paper (CRU/2025236). Commission for Regulation of Utilities (Ireland). CRU/2025236. https://cruie-live-96ca64acab2247eca8a850a7e54b-5b34f62.divio-media.com/documents/CRU2025236_Large_Energy_User_connection_policy_decision_paper.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.