MTI600 Modular UPS 60-600 kVA: User Manual
Original title MTI600 Modüler UPS 60–600 kVA: Kullanım Kılavuzu
Tescom Elektronik
Tescom's July 2024 MTI600 manual: 60-600 kVA built from 36 kg, 60 kVA power modules, output power factor 1.0, efficiency above 97% in normal mode and above 99% in ECO mode, VFI-SS-111 class.
On this page
Overview
The manual describes installation, use, operation and maintenance of the MTI600 modular UPS, an online double-conversion unit with DSP technology. The system consists of main input, static bypass, maintenance bypass and an external battery; power modules each carry a rectifier (REC), inverter (INV) and bidirectional DC-DC converter and are paralleled in a cabinet. The manual describes battery, bypass, ECO, automatic restart and frequency converter modes, UPS configurations and parallel operation.
Contents run through safety, overview, installation (environment, weight and size, cabinet transport and positioning, battery, power cables, external circuit breaker, control and communication cables), the cabinet display and main menu (power module, settings, measurement), operation (start-up, start from battery, transfers, EPO), maintenance and product specifications. The standards table lists EN 50091-1-1/IEC 62040-1-1 for safety, EN 50091-2/IEC 62040-2 (C3) for EMC and EN 50091-3/IEC 62040-3 (VFI SS 111) for performance.
The product specifications give 60-600 kVA rated capacity, 380/400/415 V three-phase four-wire, 50/60 Hz, output power factor 1.0 and voltage accuracy of +/-1%. Input power factor is above 0.99 and THDi under 3%. Efficiency is above 97% in normal mode, above 99% in ECO mode and above 96% in battery mode. It is a product manual: it puts load, battery, bypass, environment and mechanical values in one place for the designer and holds no selection or comparison.
Key points
- Capacity 60-600 kVA; power module 60 kVA, 550 x 750 x 85 mm and 36 kg; 600 kVA cabinet (bypass module included) 800 x 1100 x 2000 mm, 405 kg, IP20; the example cabinet holds 10 modules.
- Input: 380/400/415 V, 3 phase + neutral + earth, 50/60 Hz; input voltage range 323-478 VAC at full load, with load falling linearly from 100% to 30% over 138-323 VAC; input power factor above 0.99; THDi under 3%.
- Output: 60-600 kVA, power factor 1.0, voltage accuracy +/-1%, frequency 50/60 Hz +/-0.01%; THDu under 1% on 0-100% linear load and under 5% on fully non-linear load per IEC/EN 62040-3.
- Overload: 1 hour at 110%, 10 minutes at 125%, 1 minute at 150%, 200 ms above 150%; transient response under 5% for a load step and recovery under 20 ms (0-100-0%).
- Efficiency: normal mode (double conversion) above 97%, ECO mode above 99%, battery mode above 96%.
- Battery: nominal bus +/-240 V, 40 x 12 V (240 cells) for VRLA, float 2.25 V/cell, end-of-discharge 1.65 V/cell at 0.6C and 1.75 V/cell at 0.15C; charging power 30% of UPS capacity; battery count adjustable from 32 to 44.
- Environment: 0-40 degrees C (battery life halves for every 10 degrees C above 20), humidity 0-95% non-condensing, noise at 1 m 75 dB at 100% load and 70 dB at 45% load, no derating to 1000 m and 1% power loss per 100 m between 1000 and 2000 m.
- Bypass: rated 600 kVA, 110% continuous, 10 minutes at 110-125%, 1 minute at 125-150%, 200 ms above 150%; synchronous transfer 0 ms.
- Standards: EN 50091-1-1/IEC 62040-1-1, EN 50091-2/IEC 62040-2 (C3) and EN 50091-3/IEC 62040-3 (VFI SS 111).
Using it in design
- Set the module count from load growth and N+1 redundancy; with 60 kVA module steps the cabinet can be installed part-filled and expanded later.
- Match battery count (32-44 range) and charging power (30% of UPS rating) to the chosen battery cabinet and autonomy; a wrong battery-count setting risks damage.
- Keep the battery room near 20-25 degrees C; include in lifecycle cost that each 10 degrees C above 20 halves battery life.
- Before using the above-99% efficiency of ECO mode, assess the load's tolerance to the bypass transfer and the ECO voltage window setting.
- At sites above 1000 m add the 1% power loss per 100 m to capacity calculation; carry the noise values (75 dB at 1 m) into electrical room acoustic design.
- State the standard CAN, RS485, USB and dry-contact interfaces and optional SNMP and AS400 cards for communication and monitoring in the specification.
Who should read it
Turkish electrical engineers and field service technicians who install, run or specify large modular UPS.
Document contents
- Safety
- Overview (product description, system composition, operating modes, UPS configuration)
- Installation (environment, weight and size, cabinet positioning, battery, power cables, control and communication cables)
- Cabinet display panel and main menu
- Operation (start-up, transfers, EPO)
- Maintenance
- Product specifications (standards, environment, mechanical, electrical, efficiency, display and interface)
Publication details
- Authors
- Tescom Elektronik
- Publisher
- Tescom Elektronik
- Year
- 2024
- Document number
- AGKK15331 / 07/2024
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Üreticinin herkese açık kaynağı okundu. Açık erişim yeniden dağıtım izni değildir; tam metin kütüphaneye alınmaz. Tescom resmî doküman dizini tescomakademi.com PDF bağlantısını yayımlar. Son sayfada 07/2024 tarihli belge kodu vardır.
Citation
Tescom Elektronik (2024). MTI600 Modüler UPS 60–600 kVA: Kullanım Kılavuzu. Tescom Elektronik. AGKK15331 / 07/2024. https://tescomakademi.com/doc/AGKK15331.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.