Technical guideFree to read2023

15th National HVAC Engineering Congress Proceedings, Volume 4: Seismic protection and fire dampers

Original title 15. Ulusal Tesisat Mühendisliği Kongresi Bildiriler Kitabı: Cilt 4: sismik koruma ve yangın damperleri

TMMOB Makina Mühendisleri Odası

Two papers from the TESKON 2023 proceedings: seismic restraint of mechanical services costs no more than 1% of mechanical cost and 0.3% of building cost; fire dampers must be tested to EN 1366-2 or UL 555 with at least 2 hours integrity.

On this page

Overview

The document is the digital proceedings book of the 15th National HVAC Engineering Congress held by the TMMOB Chamber of Mechanical Engineers in Izmir on 26-29 April 2023 (MMO publication E/MMO/742). The theme was 'Transformation in Mechanical Installations' with 121 peer-reviewed papers. This page draws on the book's two papers on seismic protection and fire dampers; it is not a guide written specifically for data centres.

C. Volkan Dikmen's paper argues that even earthquake-resistant buildings can cause deaths if electromechanical systems lack seismic protection, noting that 65% of post-earthquake deaths occur in fires. It summarises seismic restraint rules in ASCE 7-10 Chapter 13 (IBC), NFPA 13, FEMA 412, 413, 415 and SMACNA guidance, and stresses that the Turkish seismic code gives load calculations for non-structural elements but does not say which components need protection.

Exemption rules come with concrete thresholds: floor-mounted, non-critical equipment of 180 kg or less, mounted at 120 cm or lower with flexible connections; pipes with hanger distance of 30 cm or less; pipe bundles under 15 kg/m; ducts under 15 kg/m or 0.557 m². Under NFPA 13, fire pipes of 50 mm or less may skip transverse and longitudinal bracing.

The paper by Arda Savtak, Rasim Tokgöz and Seçkin Tuncer Erdoğmuş covers fire and smoke damper positioning and EN and UL certification. EN 1366-2 testing measures integrity (E), smoke leakage (S) and insulation (I); UL 555 applies operational reliability, fire, hose stream and dynamic closure tests. Both papers address general building services and are not a current code-compliance checklist.

Key points

  1. 65% of post-earthquake deaths are said to occur in fires; the paper recommends making seismic protection of electromechanical systems mandatory by regulation.
  2. Seismic protection typically costs no more than 1% of mechanical installation cost and 0.3% of building cost; electromechanical systems have reached 25-30% of building cost.
  3. ASCE 7-10 Chapter 13 exemption: floor-mounted, Ip=1, non-critical, 180 kg or less, mounted at 120 cm or lower, flexibly connected equipment.
  4. For suspended or vibration-isolated equipment the exemption is 9 kg or less; ducts under 15 kg/m or 0.557 m² and pipe bundles under 15 kg/m may be unrestrained.
  5. NFPA 13: fire pipes of 50 mm or less may skip transverse and longitudinal bracing; free-end branch lines must be restrained.
  6. FEMA 412 (mechanical), 413 (electrical), 415 (ducts and pipes) and the SMACNA manual are recommended as practical handbooks.
  7. Fire dampers tested to EN 1366-2 are classified to EN 13501-3 as E, S and I; integrity at least 2 hours, E leakage at most 360 m³/(h.m²), S smoke leakage at most 200 m³/(h.m²) at 300 Pa.
  8. For I (insulation) the maximum temperature rise is 140-180 °C depending on the measuring point.
  9. UL 555: 250 cycles for non-motorised and 20,000 cycles for motorised dampers; 1.5 or 3 hour fire test; dynamic closure at at least 10 m/s airflow and 1,000 Pa static pressure.
  10. The purpose of fire dampers is to protect the structure and prevent the spread of fire and smoke; flash-over can be reached in under 3 minutes from ignition.

Using it in design

  • In data-centre mechanical systems (chilled-water pipes, ducts, chillers and pumps), decide which components need seismic restraint using the ASCE 7-10 Chapter 13 exemption thresholds, and add a seismic restraint drawing for seismic zones.
  • Budget seismic restraint at about 1% of mechanical cost and put specialist engineer review in the scope.
  • List NFPA 13 bracing rules (50 mm threshold, flexible connections) in the design standards for chilled-water and sprinkler piping.
  • At fire compartment boundaries require dampers certified to EN 1366-2/EN 15650 or UL 555 and state a minimum integrity period of 2 hours.
  • Check how damper closure interacts with cooling and gas-suppression zones, and define control and test scenarios.

Who should read it

Mechanical and fire-protection engineers designing data centres, and specification writers choosing seismic restraint and fire dampers in seismic regions.

Document contents

  1. Seismic protection systems for mechanical installations: calculation, design and application
  2. Fire safety in buildings and fire dampers
  3. Congress papers: pandemic, cooling, energy performance, indoor air quality, commissioning, BIM

Publication details

Authors
TMMOB Makina Mühendisleri Odası
Publisher
TMMOB Makina Mühendisleri Odası
Year
2023
Document number
MMO Yayın No. E/MMO/742, 26–29 Nisan 2023
Document language
Turkish
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher or university publicly accessible text; no open redistribution licence established. One record covers this newly reviewed volume; no duplicate records for each contained essay. Unsupported casualty percentages and normative threshold paraphrases are excluded.

Citation

TMMOB Makina Mühendisleri Odası (2023). 15. Ulusal Tesisat Mühendisliği Kongresi Bildiriler Kitabı: Cilt 4: sismik koruma ve yangın damperleri. TMMOB Makina Mühendisleri Odası. MMO Yayın No. E/MMO/742, 26–29 Nisan 2023. https://mmoteskon.org/images/2025/05/teskon-2023-bildiriler-kitabi-4.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.