CFD modelling of energy storage room fire with low-pressure water mist extinguishing
Instal · Mateusz Brzeziński, Dorota Brzezińska et al.
A 2025 Instal article: real-scale experiments and CFD simulations show that without suppression a battery fire can lead to uncontrolled temperature rise, jet flames or explosion, while water mist limits spread and temperature at adjacent modules.
On this page
Overview
The article notes that the growing use of lithium-ion batteries has made fire prevention and protection critical for users, and presents computational fluid dynamics (CFD) modelling of an energy storage room fire and its low-pressure water mist extinguishing. It follows a structured research procedure from a single cell to a full-scale energy storage facility: experimental work starts from cell and module behaviour and is extended with a computer model to a storage-room scenario.
Real-scale experiments and CFD simulations indicate that without extinguishing, battery fires can lead to uncontrolled temperature rise, jet flames or explosions. Installing a water mist system can prevent fire propagation, lower temperature and control spread to adjacent modules, even in complex battery systems. The authors distinguish limiting propagation to adjacent modules from stopping thermal runaway within an individual cell. The CFD simulations support the effectiveness of this approach in designing water mist systems for energy storage rooms.
Key points
- Subject: CFD modelling of an energy storage room fire and low-pressure water mist extinguishing.
- Without suppression a battery fire can lead to uncontrolled temperature rise, jet flames or explosion.
- A water mist system can prevent fire propagation, lower temperature and control spread to adjacent modules.
- The approach runs from single cell to full-scale facility, combining experiment and CFD.
- The authors distinguish limiting spread to adjacent modules from stopping thermal runaway in a single cell.
Using it in design
- In a battery room, define the aim of water mist design as limiting spread and temperature at adjacent modules, not stopping single-cell thermal runaway.
- Evaluate water mist effectiveness for room geometry and module layout with CFD validated by real-scale experiment.
- Model the no-suppression scenario as well (jet flame, explosion) to document the case for protection.
- If low-pressure water mist is chosen, request test and approval evidence from the manufacturer.
Who should read it
Engineers designing and modelling fire protection for battery rooms and energy storage facilities.
Publication details
- Authors
- Mateusz Brzeziński; Dorota Brzezińska; Maria Brzezińska
- Publisher
- Instal
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article landing page License section explicitly grants CC BY 4.0. Attribution and separate third-party permissions remain applicable; only metadata and original short summaries are delivered.
Citation
Mateusz Brzeziński; Dorota Brzezińska; Maria Brzezińska (2025). CFD modelling of energy storage room fire with low-pressure water mist extinguishing. Instal. https://doi.org/10.36119/15.2025.10.3