Thermal Care Aryacool+ AFW and DFW technical tables
Thermal Care
The Thermal Care Aryacool+ AFW and DFW tables show that capacity values that look identical for dry and adiabatic fluid coolers belong to different fluid and ambient air conditions.
On this page
Overview
Thermal Care presents Aryacool+ towers and adiabatic fluid coolers on its EMEA product page; the AFW and DFW technical tables show dry and adiabatic operating options side by side. The main duty in the tables follows EN 1048: pure water at 40/35°C and 25°C air.
The alternative duties use 30 percent ethylene glycol. The AFW alternative duty uses air at 35°C and 35 percent relative humidity; the DFW alternative duty uses air at 25°C. Two capacity values shown side by side can therefore belong to different fluids and air conditions and must not be compared directly.
Key points
- The main duty follows EN 1048: pure water at 40/35°C and 25°C air.
- Alternative duties use 30 percent ethylene glycol.
- The AFW alternative duty air is 35°C at 35 percent relative humidity.
- The DFW alternative duty air is 25°C.
- Capacity values that look identical for dry and adiabatic options belong to different conditions.
Using it in design
- When comparing capacity, bring fluid (pure water or 30 percent ethylene glycol) and air condition to the same basis.
- When entering AFW and DFW values in a selection table, record whether the duty is main or alternative.
- Compare the project design ambient with the 25°C and 35°C table points and ask the manufacturer for corrections.
- For glycol circuits calculate capacity loss and pump head separately.
Who should read it
Data-centre and industrial cooling engineers comparing dry and adiabatic fluid coolers.
Publication details
- Authors
- Thermal Care
- Publisher
- Thermal Care
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Thermal Care Thermal Care Aryacool+ AFW and DFW technical tables. Thermal Care. https://www.thermalcare.com/emea/products-emea/cooling-towers-and-adiabatic-fluid-coolers-emea/aryacool-emea
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.