Technical guideFree to readYear not stated

Thermoway Dry Cooler User Manual: Commissioning and Maintenance

Original title Dry Coolers User Manual

Thermoway

Thermoway's 43-page dry cooler manual: capacity on a 34% ethylene glycol basis per TS EN 1048, -40/+50°C operating range, first-start checks and a 2-6 month maintenance schedule.

On this page

Overview

The manual covers technical information, transport and storage, installation, first start, maintenance and the adiabatic cooling module for dry coolers used where process water needs cooling. The standard coil is aluminium fin on copper tube with 2.1-2.5 mm fin spacing and a staggered tube array for efficiency. Dry cooler capacities are defined on a 34% ethylene glycol by volume basis per the TS EN 1048 test method.

Selection questions to settle first are listed: water inlet and required outlet temperature, water quantity, required capacity, unit dimensions, maximum sound level at the site, energy class and fan operating temperature. The permitted operating range is -40°C to +50°C/+65°C. During long storage fans are run 2-4 hours per month. Separate sections cover horizontal, vertical and V-type use and leg installation.

The first-start section gives checklists confirming correct fluid fill with no trapped air, pressure and level matching design, correct electrical and earthing, and sensors and communications wired, and asks for operating pressure, flow, inlet and outlet temperatures and fan values to be recorded. The maintenance schedule is fan vibration checks every 3 months, fin surface cleaning every 2 months, and pressurised-water cleaning, leak and connection checks every 6 months. Below 0°C the fluid must be protected from freezing. The adiabatic module is unsuitable for ambient below 3°C and a reference water quality is defined.

Key points

  1. Capacity standard: TS EN 1048, 34% ethylene glycol by volume; aluminium fin on copper tube, fin spacing 2.1-2.5 mm.
  2. Permitted operating temperature -40°C to +50°C/+65°C; fans run 2-4 hours per month during long storage.
  3. Selection inputs: water inlet/outlet temperature, flow, capacity, size, sound level, energy class, fan operating temperature.
  4. Maintenance: fan vibration and noise checks every 3 months; fan bolts, blades, cables and motor checks every 6 months.
  5. Coil: fin surface cleaning and damage check every 2 months; pressurised-water cleaning and leak check every 6 months.
  6. Below 0°C the fluid must be protected from freezing, with glycol concentration and freezing point checked periodically; if glycol cannot be added the system is fully drained.
  7. The adiabatic system is unsuitable below 3°C ambient; feed water must be below 20°C and hot water is not used.
  8. Reference water: pH 6.5-8.0, total hardness 3.5-4.0 °d, conductivity < 1500, chloride < 50 mg/L, sulfate < 90 mg/L, nitrate < 50 mg/L, silicon < 20 mg/L, dissolved iron < 0.1 mg/L; Langelier -1 to +1, Ryznar 5.5-6.6.

Using it in design

  • Select knowing capacity rests on 34% ethylene glycol and TS EN 1048; ask for correction at a different glycol share or at high ambient.
  • Add the manual's first-start checklist and first-run data record (pressure, flow, temperatures, fan current) to the commissioning procedure.
  • Build the maintenance plan on the manual's intervals, and shorten them in dusty or dirty environments.
  • In cold climates, write glycol concentration checks and the drain plan into the operating instructions.
  • If the adiabatic module is used, include water quality limits and treatment in the design and operating plan.

Who should read it

Engineers and maintenance teams commissioning and operating dry coolers.

Document contents

  1. Technical information
  2. Transport and storage
  3. Installation and location
  4. First run
  5. Maintenance and cleaning
  6. Troubleshooting
  7. Adiabatic cooling system
  8. Water quality and operational instructions

Publication details

Authors
Thermoway
Publisher
Thermoway
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Thermoway Dry Coolers User Manual. Thermoway. https://thermoway.com.tr/wp-content/uploads/2026/08/dry-coolers-user-manual-lite.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.