Evolution of the Power Supply Unit in Data Center Servers and Key Technologies Supporting 800V DC Architecture
Texas Instruments · Desheng Guo
A March 2026 Texas Instruments technical white paper describing how server power supply units (PSUs) change in the move from 400 V AC to an 800 V DC architecture, and the technologies that enable it.
On this page
Overview
The white paper states that, with the rapid growth of AI server power needs, data-centre distribution voltage is moving from 400 V AC to 800 V DC. The long-term goal is DC microgrids integrated with solid-state transformers (SST), with rack-level PSUs replaced by an ultra-compact intermediate bus converter (IBC) in the IT tray. Because traditional equipment does not yet support 800 V DC, changing the whole infrastructure at once is difficult and risky.
The transition path it proposes is the power sidecar, which converts traditional 480 V AC to 800 V DC so that a new 800 V DC compute rack can keep working with the legacy AC infrastructure. The main focus is the PSU inside the sidecar, which carries all the functions of a traditional rack PSU. PSU requirements are grouped under efficiency, fast transient response, intelligent monitoring and cybersecurity.
The structural differences are compared in detail. A traditional power-shelf PSU has single-phase totem-pole PFC, 600 V or 650 V switches, 48 V ORing circuits and a fan supplied from the main output. An 800 V sidecar PSU has three-phase Vienna PFC, a 1200 V SiC or 650 V series topology, 800 V-rated ORing and a fan that cannot be supplied from the main output because 800 V is too high.
The paper covers GaN and SiC devices, bidirectional GaN (BDG), hybrid hysteretic-controlled LLC and high-voltage ORing control. As a manufacturer paper, its examples feature TI products and reference designs; the architecture requirements and topology comparisons can be used independently of the vendor.
Key points
- Distribution voltage is moving from 400 V AC to 800 V DC; the long-term goal is a DC microgrid with SSTs and an IBC in the IT tray.
- The top 80 PLUS class, Ruby, requires 96.5% efficiency at half load; modern data-centre PSUs pursue 98%+ peak efficiency including cooling fan power.
- GPUs switch between idle and peak within milliseconds; the Mt. Diablo 400 specification limits voltage deviation during load transients to within ±3% of the output voltage.
- 800 V sidecar PSU: three-phase Vienna PFC, 1200 V SiC or 650 V series DC-DC, 800 V-rated ORing; traditional PSU: single-phase totem-pole PFC, 600 or 650 V switches, 48 V ORing.
- Vienna PFC halves the voltage stress on power devices to half the DC-link voltage and allows mature 650 V MOSFETs.
- Totem-pole PFC reference designs (PMP40988 and PMP23475) achieve peak efficiency above 99.0%.
- A bidirectional GaN switch equals four back-to-back Si or SiC MOSFETs at the same on-resistance; the paper says it needs further market validation.
- Moving from 48 V busbars to ±400 V or ±800 V busbars reduces copper losses by lowering current.
Using it in design
- In the transition strategy, consider the sidecar approach, which keeps 480 V AC infrastructure while feeding 800 V DC racks, as an option for an existing facility.
- In the PSU specification, state half-load and peak efficiency separately, including fan power, rather than full load only.
- Verify the output-voltage tolerance for load transients (for example ±3%) and current sharing among paralleled PSUs; ask how far internal storage smooths AC-input fluctuation.
- For an 800 V bus, add ORing, hot-swap, isolated communication and separate fan supply requirements to the PSU specification.
- For intelligent PSU communication (CAN, EtherCAT, Ethernet), require encrypted protocols, signed firmware updates and access control.
Who should read it
Data-centre electrical designers evaluating the move to 800 V DC, engineers writing PSU specifications, and power-electronics designers.
Document contents
- The Evolution of Power Supply Units in Data Center Servers
- The Requirements of PSUs in Data Center Servers (higher efficiency, fast transient response driven by GPUs, intelligence and security)
- PSU Variations in 800V DC Architecture
- Key Technologies Shaping the Next Generation of PSUs (GaN, bidirectional GaN Vienna PFC, hybrid hysteretic-controlled LLC, high-voltage ORing)
- Conclusion
Publication details
- Authors
- Desheng Guo
- Publisher
- Texas Instruments
- Year
- 2026
- Document number
- STDA027
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.
Citation
Desheng Guo (2026). Evolution of the Power Supply Unit in Data Center Servers and Key Technologies Supporting 800V DC Architecture. Texas Instruments. STDA027. https://www.ti.com/lit/wp/stda027/stda027.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.