Evolution of the Power Supply Unit in Data Center Servers and Key Technologies Supporting 800V DC Architecture

Texas Instruments · Desheng Guo

A March 2026 Texas Instruments technical white paper describing how server power supply units (PSUs) change in the move from 400 V AC to an 800 V DC architecture, and the technologies that enable it.

On this page

Overview

The white paper states that, with the rapid growth of AI server power needs, data-centre distribution voltage is moving from 400 V AC to 800 V DC. The long-term goal is DC microgrids integrated with solid-state transformers (SST), with rack-level PSUs replaced by an ultra-compact intermediate bus converter (IBC) in the IT tray. Because traditional equipment does not yet support 800 V DC, changing the whole infrastructure at once is difficult and risky.

The transition path it proposes is the power sidecar, which converts traditional 480 V AC to 800 V DC so that a new 800 V DC compute rack can keep working with the legacy AC infrastructure. The main focus is the PSU inside the sidecar, which carries all the functions of a traditional rack PSU. PSU requirements are grouped under efficiency, fast transient response, intelligent monitoring and cybersecurity.

The structural differences are compared in detail. A traditional power-shelf PSU has single-phase totem-pole PFC, 600 V or 650 V switches, 48 V ORing circuits and a fan supplied from the main output. An 800 V sidecar PSU has three-phase Vienna PFC, a 1200 V SiC or 650 V series topology, 800 V-rated ORing and a fan that cannot be supplied from the main output because 800 V is too high.

The paper covers GaN and SiC devices, bidirectional GaN (BDG), hybrid hysteretic-controlled LLC and high-voltage ORing control. As a manufacturer paper, its examples feature TI products and reference designs; the architecture requirements and topology comparisons can be used independently of the vendor.

Key points

  1. Distribution voltage is moving from 400 V AC to 800 V DC; the long-term goal is a DC microgrid with SSTs and an IBC in the IT tray.
  2. The top 80 PLUS class, Ruby, requires 96.5% efficiency at half load; modern data-centre PSUs pursue 98%+ peak efficiency including cooling fan power.
  3. GPUs switch between idle and peak within milliseconds; the Mt. Diablo 400 specification limits voltage deviation during load transients to within ±3% of the output voltage.
  4. 800 V sidecar PSU: three-phase Vienna PFC, 1200 V SiC or 650 V series DC-DC, 800 V-rated ORing; traditional PSU: single-phase totem-pole PFC, 600 or 650 V switches, 48 V ORing.
  5. Vienna PFC halves the voltage stress on power devices to half the DC-link voltage and allows mature 650 V MOSFETs.
  6. Totem-pole PFC reference designs (PMP40988 and PMP23475) achieve peak efficiency above 99.0%.
  7. A bidirectional GaN switch equals four back-to-back Si or SiC MOSFETs at the same on-resistance; the paper says it needs further market validation.
  8. Moving from 48 V busbars to ±400 V or ±800 V busbars reduces copper losses by lowering current.

Using it in design

  • In the transition strategy, consider the sidecar approach, which keeps 480 V AC infrastructure while feeding 800 V DC racks, as an option for an existing facility.
  • In the PSU specification, state half-load and peak efficiency separately, including fan power, rather than full load only.
  • Verify the output-voltage tolerance for load transients (for example ±3%) and current sharing among paralleled PSUs; ask how far internal storage smooths AC-input fluctuation.
  • For an 800 V bus, add ORing, hot-swap, isolated communication and separate fan supply requirements to the PSU specification.
  • For intelligent PSU communication (CAN, EtherCAT, Ethernet), require encrypted protocols, signed firmware updates and access control.

Who should read it

Data-centre electrical designers evaluating the move to 800 V DC, engineers writing PSU specifications, and power-electronics designers.

Document contents

  1. The Evolution of Power Supply Units in Data Center Servers
  2. The Requirements of PSUs in Data Center Servers (higher efficiency, fast transient response driven by GPUs, intelligence and security)
  3. PSU Variations in 800V DC Architecture
  4. Key Technologies Shaping the Next Generation of PSUs (GaN, bidirectional GaN Vienna PFC, hybrid hysteretic-controlled LLC, high-voltage ORing)
  5. Conclusion

Publication details

Authors
Desheng Guo
Publisher
Texas Instruments
Year
2026
Document number
STDA027
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.

Citation

Desheng Guo (2026). Evolution of the Power Supply Unit in Data Center Servers and Key Technologies Supporting 800V DC Architecture. Texas Instruments. STDA027. https://www.ti.com/lit/wp/stda027/stda027.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.