TICA Fan Wall Unit: air handlers for data centres
Original title TICA Fan Wall Unit: Air Handlers for Data Center
TICA
The TICA fan wall unit is a customised EC-fan chilled-water air handler for data centres; the standard 200 kW (50,000 m³/h) and 400 kW (100,000 m³/h) sizes run on 15/21 °C water.
On this page
Overview
The brochure presents the fan wall unit for data centres from TICA, founded in 1991. TICA has five production sites in Nanjing, Tianjin, Guangzhou, Chengdu and Kuala Lumpur and over 70 sales and service outlets worldwide. Since 2003, SMARDT, part of TICA, states it has supplied more than 500 MW of cooling capacity to data centres around the world.
Because traditional precision air-conditioning has limited capacity and cannot meet the needs of large and ultra-large data centres, TICA offers customised AHUs. The fan wall gives a larger air-supply area and higher cooling density, supporting higher racks and higher IT load per unit area. The unit is highly customised.
Key features: a patented panel (low cold bridge, low air leakage), modular design, redundancy through multi-module operation, backward-curved EC centrifugal fans, integrated speed control with no external inverter, other fans unaffected during maintenance of one, a low-resistance heat exchanger and a low pPUE aim. Options: pressure-independent control valve (PICV), different air discharge directions, motorised dampers, dual-power ATS, electrode or ultrasonic humidifier and G3, G4, M5, F7 filters.
The standard table gives two sizes. Size 200: 50,000 m³/h, 200 kW net, 4 EC fans, DN65, 2,400 x 1,690 x 3,000 mm, 2,400 kg. Size 400: 100,000 m³/h, 400 kW, 8 EC fans, DN65, 4,800 x 1,690 x 3,000 mm, 4,800 kg. Conditions: indoor air 34 °C, supply 22 °C, water 15/21 °C. Standard construction is a 50 mm PU-foam galvanized panel, copper-tube aluminium-fin heat exchanger and a 3D double-tilt drain pan.
Key points
- Standard size 200: 200 kW net, 50,000 m³/h, 4 EC fans, 2,400 x 1,690 x 3,000 mm, 2,400 kg.
- Standard size 400: 400 kW net, 100,000 m³/h, 8 EC fans, 4,800 x 1,690 x 3,000 mm, 4,800 kg.
- Conditions: indoor air 34 °C, supply air 22 °C, water 15/21 °C; water connection DN65.
- Standard construction: 50 mm PU-foam panel, copper-tube aluminium-fin heat exchanger, backward EC fan (composite impeller).
- Integrated speed control with no external inverter; multiple fans back each other up.
- Options: PICV, motorised damper, dual-power ATS, electrode or ultrasonic humidifier, G3, G4, M5, F7 filters.
- Multi-module operation provides redundancy; low pPUE is targeted.
- TICA active since 1991 with five production sites; SMARDT has supplied over 500 MW of data-centre cooling.
Using it in design
- In large halls, build N+1 redundancy with 200 and 400 kW modules; set module count and fan redundancy by load profile.
- Evaluate the 15/21 °C water regime and 22 °C supply temperature together with the high-temperature design of the chilled-water plant (free-cooling hours).
- Include the PICV option on the chilled-water line to avoid low Delta-T problems.
- Carry the unit weight (2,400 and 4,800 kg) and the 3,000 mm height into the structure and plant room plan.
- Fix discharge direction, dampers, filter class and humidification requirement for the project before ordering.
Who should read it
Mechanical engineers designing fan-wall air distribution in large and ultra-large data centres.
Document contents
- Company introduction
- Fan wall unit for data centres
- Unit and EC fan features
- Intelligent controller and PICV
- Other optional parts
- Standard sizes and standard configuration
Publication details
- Authors
- TICA
- Publisher
- TICA
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
TICA TICA Fan Wall Unit: Air Handlers for Data Center. TICA. https://tica.ru/upload/iblock/e73/akz596ihye7wbaspl6pqhpveendtdyko.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
