Wuxi Tongfang R290 commercial inverter heating cooling heat pump, Technical Data
Tongfang
The Tongfang (THTF) TS500R R290 commercial inverter heat pump is a monobloc unit modulating 10-35 kW cooling (35/24°C air, 12/7°C water) and 17.56-50 kW heating with 75°C water outlet.
On this page
Overview
THTF presents the TS500R with high reliability, EVI (enhanced vapour injection) technology, an all-DC inverter design that runs stably down to -25°C, water outlet up to 75°C, R290 refrigerant and super-silent operation. Multiple operation protection guards against voltage fluctuation and overheating, alternative cycle duty and defrost operation adapt running to load, and anti-corrosion protection raises durability.
R290 (propane) is a natural refrigerant with a GWP of 3. An intelligent climate curve adjusts water temperature automatically to ambient conditions. Multiple silence modes let the user control sound level. The all-DC inverter design offers energy saving, quick start-up and less frequent start-stop cycles.
The technical table (380~415/3/50) gives: heating at A7/6°C, W30/35°C capacity 17.56-50 kW and input 2.61-12.88 kW; at A7/6°C, W47/55°C 17.95-49 kW and 3.48-17.2 kW; cooling at A35/24°C, W12/7°C 10-35 kW and 3.84-14.50 kW (current 6.42-20.56 A). ERP level A++ at 35°C outlet water, maximum input 19.84 kW and current 30.30 A, rated water flow 8.60 m³/h, water-side pressure drop at most 65 kPa, DN40 water connection, water pressure 0.1-0.3 MPa.
Physical data: one DC inverter fan, Hitachi DC inverter compressor, IPX4, 65 dB(A) at 1 m, net weight 500 kg, dimensions 1155 x 990 x 1880 mm. Operating range is -25 to 45°C ambient in heating and 16 to 45°C in cooling. The product is a commercial heat pump and is not presented as a data-centre chiller.
Key points
- Model TS500R; R290 refrigerant, GWP 3.
- Cooling at A35/24°C, W12/7°C: capacity 10-35 kW, input 3.84-14.50 kW.
- Heating at A7/6°C, W30/35°C: 17.56-50 kW, input 2.61-12.88 kW.
- Heating at A7/6°C, W47/55°C: 17.95-49 kW, input 3.48-17.2 kW.
- Maximum water outlet 75°C; maximum input 19.84 kW, current 30.30 A.
- Operating range: -25 to 45°C ambient in heating, 16 to 45°C in cooling.
- Rated water flow 8.60 m3/h; water pressure drop at most 65 kPa; DN40 connection; water pressure 0.1-0.3 MPa.
- Sound pressure 65 dB(A) at 1 m; IPX4; net weight 500 kg; 1155 x 990 x 1880 mm.
Using it in design
- Judge cooling capacity only at 35°C ambient and 12/7°C water (10-35 kW modulation); for continuous loads such as data centres check the minimum capacity limit.
- R290 is a flammable refrigerant; confirm safety distances and applicable regulation requirements for the layout with the manufacturer.
- Add the 65 kPa water-side pressure drop and 8.60 m3/h flow to pump selection.
- For heat recovery, evaluate pairing the up-to-75°C water outlet with district or building heating.
Who should read it
Mechanical designers evaluating heat pumps or small-scale cooling with heat recovery.
Document contents
- High Reliability
- Stable Operation At -25°C
- All DC Inverter
- Water Temperature Outlet Up To 75°C
- R290 Refrigerant, environment friendly
- Super Silent
- Technical Data: TS500R
Publication details
- Authors
- Tongfang
- Publisher
- Tongfang
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Tongfang Wuxi Tongfang R290 commercial inverter heating cooling heat pump, Technical Data. Tongfang. https://www.thtf-heatpump.com/r290-commercial-inverter-heating-cooling-heat-pump-product/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.