Sustainable data centre design and energy analysis
Original title Sürdürülebilir Veri Merkezi Tasarımı ve Enerji Analizi
Isparta Uygulamalı Bilimler Üniversitesi · Muhammed Burak Oyacı
A 2023 master's thesis from Isparta University of Applied Sciences designs a 500 m², 60-rack (7 kW/rack) data centre for Ankara; an 85.05 kWp rooftop PV system covers 2.07% of site consumption.
On this page
Overview
Muhammed Burak Oyacı's master's thesis, supervised by Prof. Dr. Önder Kızılkan, designs a 500 m² data centre for Ankara conditions referencing minimum Tier 3 requirements, and integrates solar power. The facility is envisaged with 60 racks of 45U at 7 kW per rack, a raised floor and cold-aisle containment. The design outdoor condition for Ankara is 34 °C dry bulb and 40% relative humidity.
The introduction summarises data-centre components, cooling equipment, containment, facility types and Uptime Institute and ASHRAE standards. The method chapter covers the PUE definition, heat gain for the white space and UPS room, UPS load and topology choice, and selection of generator, transformer, fire detection, power distribution and cooling system. The findings chapter lists the selected equipment.
Selections: white-space CRAHs at 3+3 redundancy of 176 kW each and 1+1 UPS-room CRAHs of 176 kW; total cooling load 704 kW. Two free-cooling 750 kW chillers (EER 4.07, input power 184.3 kW) are chosen, with 30% glycol in the loop. UPS load is 462 kW, served by 625 kW/kVA N+1 modular UPS, two cabinets for the A and B feeds. Generator load is 1,654.68 kVA, with 2N 1,700 kVA MTU generators and 28,800 L of fuel per generator for 72 hours.
Solar is examined in two forms. A rooftop system of 126 panels of 0.675 kWp gives 85.05 kWp DC, saves 727,102 TL per year and covers about 2.07% of consumption. A ground-mounted system meeting the whole demand needs 6,192 panels and 43 inverters of 100 kW, and saves 35,066,455 TL per year. For critical facilities the thesis recommends grid-supported rather than standalone PV, with a grid-connected design because battery cost would double the initial investment.
Key points
- Design: Ankara, 500 m², 60 racks of 45U at 7 kW each, minimum Tier 3, raised floor and cold-aisle containment.
- Ankara design outdoor condition: 34 °C dry bulb, 40% relative humidity.
- White-space CRAHs 3+3 at 176 kW each; UPS-room 1+1 at 176 kW; total cooling load 704 kW.
- Two free-cooling 750 kW chillers, EER 4.07, input power 184.3 kW; 30% glycol.
- UPS load 462 kW; 625 kW/kVA N+1 modular UPS (250 kW cabinets, 50 kW modules); two units for A and B feeds.
- Generator load 1,654.68 kVA; 1,700 kVA MTU, 2N; 72 hours at 400 L/h needs a 28,800 L tank.
- Rooftop PV: 126 panels x 0.675 kWp = 85.05 kWp DC; AC system efficiency 86.67%; 727,102 TL per year saved; about 2.07% of consumption.
- Ground PV: 6,192 panels and 43 inverters of 100 kW; 35,066,455 TL per year saved; electricity price 3.78 TL/kWh.
Using it in design
- For a mid-size hall, set white-space and UPS-room cooling loads separately by heat gain calculation; the thesis's 704 kW for 60 racks at 7 kW is a scale example.
- In UPS selection, weigh the computed load (462 kW) against growth and the efficiency curve around 50% load, and prefer a modular N+1 architecture.
- Compute generator load as the sum of UPS, chiller, CRAH and pump loads with demand factors, and size the fuel tank for the target autonomy.
- Treat PV as a grid-supported rather than standalone source; with limited roof area expect only a few percent of consumption.
- Check the combination of cold-aisle containment and free-cooling chillers with annual free-cooling hours for a cold-winter climate like Ankara.
Who should read it
Engineers and students wanting to follow end-to-end design steps (heat gain, UPS, generator, chiller, PV) for a mid-size, Tier 3 target data centre.
Document contents
- Introduction (data centre, components, efficiency methods, types, standards, solar generation)
- Literature review
- Materials and method (PUE, design data, heat gain, UPS load and topology, generator, transformer, fire, power transfer, cooling and PV selection)
- Findings and discussion (CRAH, UPS, chiller, generator, fire detection, automation, PV)
- Conclusions and recommendations
Publication details
- Authors
- Muhammed Burak Oyacı
- Publisher
- Isparta Uygulamalı Bilimler Üniversitesi
- Year
- 2023
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Open university PDF obtained through the public stable AVESIS file resolver. YÖK thesis number and direct YÖK permission flag remain unverified.
Citation
Muhammed Burak Oyacı (2023). Sürdürülebilir Veri Merkezi Tasarımı ve Enerji Analizi. Isparta Uygulamalı Bilimler Üniversitesi. https://avesis.isparta.edu.tr/dosya?id=79adec46-8420-4f8b-bcac-5f5c87176105
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
